Final | 3/30/2015 | 3/31/2015 | 3/31/2015 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Gerald McLain correction done, final ok
|
Electrical Rough-In | 3/30/2015 | 3/31/2015 | 3/31/2015 | P | PASS |
Daryl DeGrange
|
|
|
ceiling rough re-inspection Phone #: ###-#### Inspection requested via web by Gerald McLain rough-in ok cover ceiling grid
|
Electrical Rough-In | 3/29/2015 | 3/30/2015 | 3/30/2015 | P | FAIL |
Bob Reichert
|
|
|
CEILING ROUGH ELECTRICAL INSPECTION Phone #: ###-#### Inspection requested via web by Gerald McLain left correction notice, told wireman to be sure and have license on person, NEC 725.25 shall remove abandoned lv cables,300.11 grid shall not support cables and raceways
|
Electrical Rough-In | 3/12/2015 | 3/12/2015 | 3/12/2015 | A | PASS |
Daryl DeGrange
|
|
|
correction done,Rough-in ok cover walls
|
Electrical Rough-In | 3/10/2015 | 3/11/2015 | 3/11/2015 | P | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Gerald McLain NEC 330.30(A) Securing MC cable witin 12 in. od cable termination, NEC 362.12(9) Uses not permited, Where subject to physical damage.
|