Permit NumberELE17-04065
StatusFinaled
Name R M E INC
Site Address 201 W JEFFERSON ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Install power and lighting per drawings
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/14/20188/15/20188/14/2018APASS
DetailsRock A. Hudson
Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Corrections complete. Final ok
Electrical Rough-In8/14/20188/14/20188/14/2018PPASS
DetailsRock A. Hudson
Ceiling Cover... Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Back patios level 1 and 2 grid rough in ok cover
Level 1 and 2 patio
Final7/10/20187/11/20187/11/2018AFAIL
DetailsRock A. Hudson
Looking for a TCO. Please come as early as possible. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
110.3- Outdoor receptacles not working.
110.3- Level 2 (Kim D office) receptacle outlets not working.
110.3- Baseboard manufacurers instructions state receptacle outlets shall not be installed over baseboard heaters.
110.26- Level 2 (Kim D office) Minimum work space shall be provided for panel K2-P1. Built in desk installed in front of panel.
210.70(A)(2)- Each door with access to exterior shall have a luminaire installed for egress.
300.15- All wiring shall terminate in a box. Patio light wires.
314.25- All boxes shall have covers. Light box over stair and wire for light over door.
BCC 4 05 17- Unlawful electrical procedures. All work to be performed by a licensed electrical contractor. It has been reported some receptacles were changed by an unlicensed person.
Electrical Rough-In6/26/20186/26/20186/26/2018PPASS
DetailsRock A. Hudson
Wall Cover and ceiling on floors 1 and 2. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 1 and 2 back patios walls and emergency light and occ sensor grid rough in ok cover
Electrical Rough-In6/22/20186/25/20186/25/2018APASS
DetailsRock A. Hudson
Ceiling cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Basement grid rough in ok cover
Electrical Rough-In6/21/20186/22/20186/22/2018AFAIL
DetailsRock A. Hudson
Ceiling Cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
330.30- MC shall be supported independant of grid. All luminaires shall be secured to structure basement. Call contact he stated he wanted to reschedule for monday anyway. Will recall when ready.
Electrical Rough-In6/21/20186/22/20186/21/2018ACANC
DetailsRock A. Hudson
Ceiling cover. Danny is the contact Phone #: ###-#### >> Inspection requested via web by Buster Bowen Inspection cancelled from web by: Buster Bowen
Electrical Rough-In6/15/20186/18/20186/18/2018APART
DetailsRock A. Hudson
Ceiling cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Levels 1 and 2 only basement not ready gri as noted rough in ok cover
Electrical Rough-In1/23/20181/23/20181/23/2018APASS
DetailsRock A. Hudson
Wall Cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Main level and basement wall rough in ok cover
Electrical Rough-In1/12/20181/16/20181/16/2018APASS
DetailsRock A. Hudson
Wall Cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 2 and 3 walls and hardlid rough in ok cover
Conference12/7/201712/7/201712/7/2017PDONE
DetailsRock A. Hudson
As per head structural Bob Archibald. Due to plan review on building permit being completed prior to 7-1-17 the 2014 version of NEC will apply.
Permanent Service12/4/201712/4/201712/4/2017PPASS
DetailsRock A. Hudson
Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
p/s u/g n ok