Final | 7/20/2018 | 7/20/2018 | 7/20/2018 | P | PASS |
James Ady
|
|
|
Von is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Final ok
|
Final | 6/25/2018 | 6/26/2018 | 6/26/2018 | A | PART |
James Ady
|
|
|
Please call Von 1/2 prior to arrival. Phone #: ###-#### Inspection requested via web by Buster Bowen Need Exit sign over back door and Lock out on disposal. Temp only ok
|
Electrical Rough-In | 6/12/2018 | 6/12/2018 | 6/12/2018 | A | PASS |
Rock A. Hudson
|
|
|
Ceiling cover. Von is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Grid rough in ok cover
|
Electrical Rough-In | 6/11/2018 | 6/11/2018 | 6/11/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Ceiling cover. Von is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen 300.15- MC cable shall terminate in a box. 1 area behind reception 1 in office out of wall. 300.11- MC and other cable shall be supported insependant of grid. Fixture whip and low volt.
|
Electrical Rough-In | 4/25/2018 | 4/26/2018 | 4/26/2018 | A | PASS |
Rock A. Hudson
|
|
|
Wall Cover. Von is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Wall rough in ok cover
|