Information based on query as of Wednesday, May 15, 2024.
Permit Information
Permit NumberELE18-01642
StatusFinaled
Name AHLIN JUSTIN W
Site Address 4424 W ALPINE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Panel swap & addition of 100amp sub panel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/12/20194/15/20194/15/2019APASS
DetailsRock A. Hudson
Justin Phone #: ###-#### Final ok
Final4/11/20194/11/20194/11/2019PFAIL
DetailsRock A. Hudson
Justin Phone #: ###-####
314.20- Boxes mounted in a combustible materials shall be flush with such materials or have an extension ring installed.
406.9(B)- Receptacles installed in wet locations shall be weather resistant type and have a in use cover identified as extra duty.
406.12- All 15 or 20 amp 120 volt receptacles installed in or on a residential building shall be tamper resistant type.
Final4/10/20194/10/20194/10/2019PNH
DetailsRock A. Hudson
Justin Phone #: ###-####
Called 12:58pm, left message, was in area 25 minutes, no longer in area, please reschedule another day.
Electrical Rough-In1/22/20191/22/20191/22/2019PPASS
DetailsJames Ady
Justin Phone #: ###-#### Shop rough in ok to cover
Electrical Rough-In5/21/20185/21/20185/21/2018PPASS
DetailsRock A. Hudson
Underground & rough in - Justin Phone #: ###-####
Seperation of grounds and neutrals at each shop location. All wiring existing may relocate 2 kiln circuits. Underground rough in ok cover
Conference5/1/20185/1/20185/1/2018PDONE
DetailsRock A. Hudson
Justin Phone #: ###-####
Discussed the replacement of a panel in one shop and sub-feeding another shop. A 200 amp 40 circuit main breaker panel going in green shop and a 100 amp sub to 2nd shop. Concrete encased electrode exists in green shop, 2nd shop will need 2 ground rods 6' or more apart. Discussed wire sizes and types of wiring meathods for underground, burial depth, and disconnecting means for each structure.