Name COMMERCIAL ELECTRIC INC
Site Address 11350 W FRANKLIN RD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: ELE FOR NEW IPCO CONTROL BLDG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/28/201811/29/201811/29/2018APASS
DetailsTom Saunders
Thank you. Phone #: ###-#### Inspection requested via web by CHRIS CARMINE...
corrections made...ok to final
final is for shell wiring only...interior wiring is ID Power training center
Final11/27/201811/28/201811/28/2018PFAIL
DetailsRock A. Hudson
Thank you. Phone #: ###-#### Inspection requested via web by CHRIS CARMINE
210.8(B)- All single phase receptacles and 3 phase receptacles 150 volts or less to ground located outdoors shall have GFCI protection.
422.31(B)- Permanently connected appliances rated 300 va or more shall have a disconnecting means located with in 50' and with in sight.
110.25 lock out acceptacle.
Electrical Rough-In10/30/201810/31/201810/31/2018PPASS
DetailsTom Saunders
Thank you. Phone #: ###-#### Inspection requested via web by CHRIS CARMINE...ceiling ok to cover-training building
Electrical Rough-In9/6/20189/7/20189/7/2018APASS
DetailsTom Saunders
UFER PLEASE. THANKS Phone #: ###-#### Inspection requested via web by CHRIS CARMINE....concrete encased rebar..ok to cover