Final | 1/15/2019 | 1/16/2019 | 1/16/2019 | A | PASS |
Rock A. Hudson
|
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
Permanent Service | 11/1/2018 | 11/1/2018 | 11/1/2018 | P | PASS |
James Ady
|
|
|
Permanent service p/s u/g n ok
|
Rough-In Permanent Service | 9/20/2018 | 9/21/2018 | 9/21/2018 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn corrections made rough in ok
|
Rough-In Permanent Service | 9/19/2018 | 9/20/2018 | 9/20/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Attic upstairs boxes trimmed at rough in, christmas switches located in entry closet, 327 has pics of 12-2 stubs in family room off kitchen. 250.24- Grounding electrode conductor connection shall connect to grounded conductor in 1 location only. Jumper installed from main breaker panel to meter base creating parallel path between grounded conductor and grounding conductor. 250.68(A)- Connection to concrete encased electrode shall remain accessible. Need mudring. 300.4- Where NM cable is run through bored holes that do not maintain 1 1/4" from framing surface they shall be protected by nail plates. By garage man door, above mudroom switches, pantry wire to under stair light. 348.26- Maximum number of bends in FMC to single garage attic shall not exceed 360 degrees.
|