Information based on query as of Monday, May 6, 2024.
Permit Information
Permit NumberELE18-03596
StatusFinaled
Name JES ELECTRIC
Site Address 4252 W ROSE HILL ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Underground Only
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/19/20196/19/20196/19/2019PPASS
DetailsEric Story
Final for U/G on project ok
Final6/13/20196/14/20196/14/2019AFAIL
DetailsEric Story
This Is Ready For Final Please Call Me With Any Issues Phone #: ###-#### Inspection requested via web by jason shifflett
Room ID required
210.12 AFCI protection required
410 Luminaires shall not be within 6" of shelving on LED fixtures unless rated
210.8 All receptacles located withn 6' of a sink shall have GFCI protection
Manufact spec required for connectors used on type MC connectors on mini split units.....
Final9/19/20189/19/20189/19/2018PCANC
DetailsEric Story
Dave Phone #: ###-####
Needed R/I
Rough-In Permanent Service9/19/20189/19/20189/19/2018PPASS
DetailsEric Story
Dave Phone #: ###-####
U/G along side of of bui;ding ok to cover