Permit Information
Permit NumberELE18-03892
StatusFinaled
Name ETTA QUALLS
Site Address 4702 W GAGE ST
Project Name4702 W Gage St
Customer Number 
ePlanReviewNo
Description
complete installation
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/11/20193/11/20193/11/2019PPASS
DetailsRock A. Hudson
Etta Phone #: ###-#### Final ok
Final3/7/20193/8/20193/8/2019PFAIL
DetailsRock A. Hudson
Etta Phone #: ###-####
110.3- Open ground and up receptacle not working. Mechanical room and pantry show open grounds.
250.140- Range and dryers shall be 4 wire receptacles.
210.70- Exterior lights shall operate at all exterior entrances. finish patio ceiling.
314.16- Disposal box shall have 16 cubic inch minimum for conductors installed.
314.29- Boxes shall be fully accessible under cooktop.
334.12- NM cable shall be protected from damage under sink and shall not be installed in damp locations. Patio.
348.30- Strap furnace flex with in 12" of a box and rest not to exceed 3'.
406.6- Receptacles and switches shall have proper covers. few missing.
406.9- Receptacles installed outdoors shall be weather resistant type. Near AC.
422.31- Appliances shalll have a disconnecting means. 110.25 lockouts acceptable. Oven, dishwasher, range hood.
440.11- Furnace shall have a manual disconnecting means.
Permanent Service11/27/201811/28/201811/28/2018APASS
DetailsRock A. Hudson
Etta Phone #: ###-####
p/s o/h n ok
Electrical Rough-In10/31/201811/1/201811/1/2018PPASS
DetailsRock A. Hudson
Etta Phone #: ###-####
Corrections done. Rough in ok cover
Electrical Rough-In10/29/201810/29/201810/29/2018PFAIL
DetailsDaryl DeGrange
call 20 mins head- Etta Phone #: ###-#### Complete all make-ups
NEC 334.30 Sscure NM within 12in. of entry of outlet boxes.
KO Plug
Nail plates where needed.
Grounding of metal boxes
Conference10/10/201810/11/201810/11/2018APASS
DetailsRock A. Hudson
after 9am- Etta Phone #: ###-####
Owners father doing work, Discussed receptacle layouts includes upstair rail and fixed panel of sliding doors, each bathroom on dedicated 20 amp circuits, grounding electrode bent over to interior of crawl space, max height of breaker handles, secure support of NM cable, pamphlet given