Information based on query as of Tuesday, May 14, 2024.
Permit Information
Permit NumberELE18-04603
StatusFinaled
Name BICANDI ELECTRIC LLC
Site Address 4424 W EMERALD ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: New house
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/28/20198/29/20198/29/2019APASS
DetailsDaryl DeGrange
Phone #: ###-#### Inspection requested via web by TOM BICANDI Correction complete, Final ok
Final8/23/20198/26/20198/26/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by TOM BICANDI
356.30(1)- LFNC when installed in lengths greater than 6' shall have supports not to exceed 3' in length. AC
440.6- Overcurrent protection for AC unit shall not exceed value on name plate. 25 amp max 30 amp installed.
Rough-In Permanent Service5/24/20195/24/20195/24/2019PPASS
DetailsRock A. Hudson
Tom Phone #: ###-####
Underground to service not connected to service. Garage rough in ok cover p/s u/g n ok
Electrical Rough-In12/1/201812/3/201812/3/2018APASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by TOM BICANDI
House only ok to cover