Permit Information
Permit NumberELE18-04702
StatusFinaled
Name SUBLIME ELECTRIC LLC
Site Address 109 N MANVILLE ST
Project Name 
Customer NumberRattler Co
ePlanReviewNo
Description
Alteration or Repair: Service change & wire for remodel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/29/20195/29/20195/29/2019PPASS
DetailsRock A. Hudson
Call the office ###-#### to have someone meet you there. If you have any questions please feel free to contact Clay ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Final ok
Final5/29/20195/29/20195/29/2019ANH
DetailsRock A. Hudson
Call Clay ###-#### to meet you there. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
House locked no access. Will recall. Contractor service calculation equals 115 amps, 125 amp main. OK.
Final5/23/20195/23/20195/23/2019PFAIL
DetailsRock A. Hudson
It will be open. If you have any questions please feel free to contact Jason ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
110.22- label furnace disconnect.
210.52(C)- Counter top spaces located in pantry shall have receptacle outlets installed so that no point measured along wall line is more than 24" from a receptacle outlet.
314.25- All boxes shall have covers. Master bath switch and fan near shower.
406.5- Receptacles shall be securely mounted in place. kitchen counter near back man door.
230.79- Service disconnecting means shall not be less than calculated load to be carried. As noted prior... service calculation required for addition of hot tub.
Electrical Rough-In2/19/20192/20/20192/20/2019APASS
DetailsRock A. Hudson
There is a lock box on the back shop door, code 2020. If you have any questions please feel free to contact Luke ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
Discussed with contractor service calculation results in approx. 140 amp minimum service needed for an additional branch circuit for hot tub. Contractor to increase service or prove calculation less than what exists by final.
House rewire rough in ok cover
Electrical Rough-In2/18/20192/19/20192/19/2019AFAIL
DetailsRock A. Hudson
Lock box is on the back shop door, code 2020. If you have any questions please feel free to contact CJ ###-####. Thanks!!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
210.52(A)- No point measured along floor line shall be more than 6' from a receptacle oulet. living room north of entrance.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates.
* Service calculation needed for addition of hot tub.