Permit Information
Permit NumberELE19-00184
StatusFinaled
Name GLENN ELECTRIC
Site Address 1408 N GARDEN ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/25/20194/26/20194/26/2019APASS
DetailsEric Story
GARAGE CODE 7573 Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok
Electrical Rough-In3/15/20193/15/20193/15/2019APASS
DetailsEric Story
Floor heat master bathroom, garage code is 7573. Please contact Bob with any questions.
Thank! Phone #: ###-#### Inspection requested via web by Bob Glenn
Floor heat ok to cover
Rough-In Permanent Service1/17/20191/18/20191/18/2019APASS
DetailsJames Ady
corrections made, ceiling furred down, call mike for any questions Phone #: ###-#### Inspection requested via web by Bob Glenn corrections made rouhgh in ok p/s u/g n ok
Rough-In Permanent Service1/16/20191/16/20191/16/2019PFAIL
DetailsRock A. Hudson
The ceiling in the bottom of the garage stairs will be furred down so its flat, we have 2 can lights and a smoke detector/ CO2 combo going in there when the fur down is done Phone #: ###-#### Inspection requested via web by Bob Glenn
210.52(A)- In habitable rooms no point measured along floor line shall be more than 6' from a receptacle outlet. Up rec room 13' between receptacle outlets.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage by nail plates. Top of house stair in be at floor level marked with X and at bottom of house stair above switches where drill at 45 degree angle.