Information based on query as of Tuesday, May 14, 2024.
Permit Information
Permit NumberELE19-00485
StatusFinaled
Name MOUNTAIN VALLEY ELECTRIC
Site Address 3848 N SANDPOINT WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/2/20195/2/20195/2/2019PPASS
DetailsMark Moncarr
garage code 6365 Phone #: ###-#### Inspection requested via web by Dan Rohl Ok final. There is a recept in mstr closet next adjacent to shower. Shower is to have a floor to ceiling fixed glass panel installed.
Electrical Rough-In2/13/20192/14/20192/14/2019APASS
DetailsMark Moncarr
need ok to cover pool room Phone #: ###-#### Inspection requested via web by Dan Rohl Some of the needed corrections were completed. Another inspection will be needed to confirm bond to 1 corner of pools metal frame, and a perimeter bond on the floor 18"-24" from inside waters edge. When hardy board is installed call for floor cover.
Rough-In Permanent Service2/8/20192/11/20192/11/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jason Allen
Questions concerning permanent pool installed indoors.
A disconnecting means shall be located as per 680.13. 1 shall be located above floor and 1 shall be located below floor with in site of equipment due to equipment cover when removed gives access to equipment from above floor and below floor.
Receptacles shall not be located with in 6' of the pool waters edge as per 680.22(A)(3).
Luminaires shall be installed as per 680.22(B)(2).
Permeter surfaces shall be bonded horizonally from waters edge and 5' in height of a permanent wall on pool side only as per 680.26(B)(2).
Metellic components of pool pad (rebar) shall be bonded as per 680.26(B)(3).
House rough in except pool room rough in ok cover p/s u/g n ok