Final | 5/2/2019 | 5/2/2019 | 5/2/2019 | P | PASS |
Mark Moncarr
|
|
|
garage code 6365 Phone #: ###-#### Inspection requested via web by Dan Rohl Ok final. There is a recept in mstr closet next adjacent to shower. Shower is to have a floor to ceiling fixed glass panel installed.
|
Electrical Rough-In | 2/13/2019 | 2/14/2019 | 2/14/2019 | A | PASS |
Mark Moncarr
|
|
|
need ok to cover pool room Phone #: ###-#### Inspection requested via web by Dan Rohl Some of the needed corrections were completed. Another inspection will be needed to confirm bond to 1 corner of pools metal frame, and a perimeter bond on the floor 18"-24" from inside waters edge. When hardy board is installed call for floor cover.
|
Rough-In Permanent Service | 2/8/2019 | 2/11/2019 | 2/11/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Allen Questions concerning permanent pool installed indoors. A disconnecting means shall be located as per 680.13. 1 shall be located above floor and 1 shall be located below floor with in site of equipment due to equipment cover when removed gives access to equipment from above floor and below floor. Receptacles shall not be located with in 6' of the pool waters edge as per 680.22(A)(3). Luminaires shall be installed as per 680.22(B)(2). Permeter surfaces shall be bonded horizonally from waters edge and 5' in height of a permanent wall on pool side only as per 680.26(B)(2). Metellic components of pool pad (rebar) shall be bonded as per 680.26(B)(3). House rough in except pool room rough in ok cover p/s u/g n ok
|