Permit Information
Permit NumberELE19-00594
StatusFinaled
Name POWERHOUSE ELECTRIC
Site Address 2731 N CARMEN AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: New Home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/20/20196/21/20196/21/2019APASS
DetailsTom Saunders
garage code 2019 Phone #: ###-#### Inspection requested via web by Darryn Coburn....corrections made ok to final
Final6/17/20196/18/20196/18/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.3- Devices shall be wired as per manufacturers instructions. Reverse polarity in laundry.
210.8(A)(2)- Unfinished space off garage receptacles shall have GFCI protection.
314.16- Boxes shall have sufficient subic inch rating for conductors installed. Island receptacle box 8 cubic inches with 11.25 of conductor cubic inch installed.
348.30- FMC shall be secured with in 12" of a termination. Furnace, disposal.
406.5- Master bed USB receptacle shall be flush or project from face plate.
Rough-In Permanent Service3/4/20193/4/20193/4/2019PPASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Darryn Coburn...
rough ok to cover
p/s u/g new ok