Final | 6/24/2019 | 6/25/2019 | 6/25/2019 | P | PASS |
Rock A. Hudson
|
|
|
garage code 0555 Phone #: ###-#### Inspection requested via web by Jay Hutchison Final ok
|
Final | 6/21/2019 | 6/24/2019 | 6/24/2019 | A | FAIL |
Tom Saunders
|
|
|
garage code 0555 Phone #: ###-#### Inspection requested via web by Jay Hutchison... 1) furnace needs disconnect...not within sight of OCPD 2)outlet in garage cabinet needs properly attached to box with proper arc protection..box resessed 3) east outlet in garage needs proper attachment to bos...tightened 4) ironing board outlet shows open ground 5) oven breaker does not match nameplate rating 6) can in master bedroom not operational 7) no access to master bath and closet at time of inspection 8) all bedroom circuits shall have AFCI protection 9) all openings in bedrooms shall have AFCI protection-switches for back patio lights
|
Rough-In Permanent Service | 2/21/2019 | 2/21/2019 | 2/21/2019 | P | PASS |
Tom Saunders
|
|
|
Jay Phone #: ###-####... rough ok to cover p/s u/g new ok
|