Final | 5/6/2019 | 5/6/2019 | 5/6/2019 | A | PASS |
Rock A. Hudson
|
|
|
We will be on job site contact Jason Phone #: ###-#### Inspection requested via web by robert feller Final ok
|
Final | 5/2/2019 | 5/3/2019 | 5/3/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Will be on site all day Phone #: ###-#### Inspection requested via web by robert feller 110.3- Misc receptacles not working on south or cable walls. 110.26(D)- Luminaires installed for required illumination for electrical equipment shall not operate by automatic means. Remove motion sensors. 210.8(B)(7)- All 15 or 20 amp receptacle outlets located in locker rooms associated with shower areas shall have GFCI protection. TV receptacles. 250.64(E)- Grounding electrode conductors installed in ferrous metal raceways shall clamp to conductor at each end by fittings for clamps. 314.20- Where boxes are recessed in non combustible wall cover 1/4" or more they shall have spark rings installed. Bathrooms, south or cable walls. 700.3- Emergency lighting and exit signs shall operate when tested.
|
Permanent Service | 4/29/2019 | 4/30/2019 | 4/30/2019 | A | PASS |
Tom Saunders
|
|
|
We will be on site need service inspected Phone #: ###-#### Inspection requested via web by robert feller... p/s u/g ok...existing service used powering new circuits
|
Electrical Rough-In | 4/30/2019 | 4/30/2019 | 4/30/2019 | A | PASS |
Tom Saunders
|
|
|
We will be on site need service inspected Phone #: ###-#### Inspection requested via web by robert feller... new transformers and panels off existing service grounding, bonding, and seperation neutrals verified rough ok
|
Electrical Rough-In | 4/29/2019 | 4/29/2019 | 4/29/2019 | P | PASS |
Tom Saunders
|
|
|
Need ceiling inspected for cover, LV contractor will have his work done. Phone #: ###-#### Inspection requested via web by robert feller... grid areas complete...ok to cover
|
Electrical Rough-In | 4/26/2019 | 4/29/2019 | 4/29/2019 | A | NR |
Tom Saunders
|
|
|
We need a partial ceiling inspection so they can install tiles. Be on site Jason will be there Phone #: ###-#### Inspection requested via web by robert feller... not ready...LV guys still working with cable on grid will schedule once other contractors complete
|
Electrical Rough-In | 4/22/2019 | 4/22/2019 | 4/22/2019 | P | PASS |
Tom Saunders
|
|
|
Need treadmill walls inspected for cover, Jason will be on site Phone #: ###-#### Inspection requested via web by robert feller... 3 sections ok to cover...pvc pipe to boxes...equipment ground will be ran...circuit per outlet
|
Electrical Rough-In | 3/26/2019 | 3/27/2019 | 3/27/2019 | A | PASS |
James Ady
|
|
|
Need the rest of walls inspected for cover will be on site Phone #: ###-#### Inspection requested via web by robert feller womans locker room and Back hallway. Walls only ok to cover
|
Electrical Rough-In | 3/21/2019 | 3/22/2019 | 3/22/2019 | A | PASS |
Eric Story
|
|
|
Will be on site need some more walls inspected for sheetrock. Phone #: ###-#### Inspection requested via web by robert feller Changing room and bath back west area ok to cover walls and hard lids with cans installed
|
Electrical Rough-In | 3/15/2019 | 3/18/2019 | 3/18/2019 | A | PASS |
Tom Saunders
|
|
|
Be on job site have more walls to inspect thanks. Phone #: ###-#### Inspection requested via web by robert feller... wall cover- massage rms, tanning rms, comm rm, and front upper entry wall for exit sign
|
Electrical Rough-In | 3/14/2019 | 3/15/2019 | 3/15/2019 | A | PASS |
Tom Saunders
|
|
|
We will be on job site contact Jason need partial wall inspection so they can sheetrock thanks. Phone #: ###-#### Inspection requested via web by robert feller... ok to cover large seperation wall
|
Electrical Rough-In | 3/1/2019 | 3/4/2019 | 3/4/2019 | A | PASS |
Mark Moncarr
|
|
|
Need some walls inspected for sheetrock cover, Jason will be on site his phone number 208-577 7115 Phone #: ###-#### Inspection requested via web by robert feller Ok cover front wall reception area, and W wall to rear of building.
|
Electrical Rough-In | 2/22/2019 | 2/25/2019 | 2/25/2019 | A | PASS |
Tom Saunders
|
|
|
We will be on site, have a couple of trenches saw cut in concrete need inspect pvc conduits for cover. Phone #: ###-#### Inspection requested via web by robert feller... ok to cover...outlets for treadmills 2 locations
|