Information based on query as of Thursday, May 16, 2024.
Permit Information
Permit NumberELE19-00672
StatusFinaled
Name M & B ELECTRIC
Site Address 1123 N MILWAUKEE ST
Project NamePLANET FITNESS, MARKETPLACE
Customer Number 
ePlanReviewNo
Description
New: TI in existing space new panels,lights, outlets and other misc.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/6/20195/6/20195/6/2019APASS
DetailsRock A. Hudson
We will be on job site contact Jason Phone #: ###-#### Inspection requested via web by robert feller Final ok
Final5/2/20195/3/20195/3/2019PFAIL
DetailsRock A. Hudson
Will be on site all day Phone #: ###-#### Inspection requested via web by robert feller
110.3- Misc receptacles not working on south or cable walls.
110.26(D)- Luminaires installed for required illumination for electrical equipment shall not operate by automatic means. Remove motion sensors.
210.8(B)(7)- All 15 or 20 amp receptacle outlets located in locker rooms associated with shower areas shall have GFCI protection. TV receptacles. 250.64(E)- Grounding electrode conductors installed in ferrous metal raceways shall clamp to conductor at each end by fittings for clamps.
314.20- Where boxes are recessed in non combustible wall cover 1/4" or more they shall have spark rings installed. Bathrooms, south or cable walls.
700.3- Emergency lighting and exit signs shall operate when tested.
Permanent Service4/29/20194/30/20194/30/2019APASS
DetailsTom Saunders
We will be on site need service inspected Phone #: ###-#### Inspection requested via web by robert feller...
p/s u/g ok...existing service used powering new circuits
Electrical Rough-In4/30/20194/30/20194/30/2019APASS
DetailsTom Saunders
We will be on site need service inspected Phone #: ###-#### Inspection requested via web by robert feller...
new transformers and panels off existing service
grounding, bonding, and seperation neutrals verified
rough ok
Electrical Rough-In4/29/20194/29/20194/29/2019PPASS
DetailsTom Saunders
Need ceiling inspected for cover, LV contractor will have his work done. Phone #: ###-#### Inspection requested via web by robert feller...
grid areas complete...ok to cover
Electrical Rough-In4/26/20194/29/20194/29/2019ANR
DetailsTom Saunders
We need a partial ceiling inspection so they can install tiles. Be on site Jason will be there Phone #: ###-#### Inspection requested via web by robert feller...
not ready...LV guys still working with cable on grid
will schedule once other contractors complete
Electrical Rough-In4/22/20194/22/20194/22/2019PPASS
DetailsTom Saunders
Need treadmill walls inspected for cover, Jason will be on site Phone #: ###-#### Inspection requested via web by robert feller...
3 sections ok to cover...pvc pipe to boxes...equipment ground will be ran...circuit per outlet
Electrical Rough-In3/26/20193/27/20193/27/2019APASS
DetailsJames Ady
Need the rest of walls inspected for cover will be on site Phone #: ###-#### Inspection requested via web by robert feller womans locker room and Back hallway. Walls only ok to cover
Electrical Rough-In3/21/20193/22/20193/22/2019APASS
DetailsEric Story
Will be on site need some more walls inspected for sheetrock. Phone #: ###-#### Inspection requested via web by robert feller
Changing room and bath back west area ok to cover walls and hard lids with cans installed
Electrical Rough-In3/15/20193/18/20193/18/2019APASS
DetailsTom Saunders
Be on job site have more walls to inspect thanks. Phone #: ###-#### Inspection requested via web by robert feller...
wall cover- massage rms, tanning rms, comm rm, and front upper entry wall for exit sign
Electrical Rough-In3/14/20193/15/20193/15/2019APASS
DetailsTom Saunders
We will be on job site contact Jason need partial wall inspection so they can sheetrock thanks. Phone #: ###-#### Inspection requested via web by robert feller...
ok to cover large seperation wall
Electrical Rough-In3/1/20193/4/20193/4/2019APASS
DetailsMark Moncarr
Need some walls inspected for sheetrock cover, Jason will be on site his phone number 208-577 7115 Phone #: ###-#### Inspection requested via web by robert feller Ok cover front wall reception area, and W wall to rear of building.
Electrical Rough-In2/22/20192/25/20192/25/2019APASS
DetailsTom Saunders
We will be on site, have a couple of trenches saw cut in concrete need inspect pvc conduits for cover. Phone #: ###-#### Inspection requested via web by robert feller...
ok to cover...outlets for treadmills 2 locations