Final | 4/11/2019 | 4/12/2019 | 4/11/2019 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt...finaled 4/11/19
|
Final | 4/11/2019 | 4/11/2019 | 4/11/2019 | P | PASS |
Tom Saunders
|
|
|
reinspect...corrections made...ok to final
|
Final | 4/9/2019 | 4/10/2019 | 4/10/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt 300.15- All cables shall terminate in a box. Dishwasher not hooked up. 406.6- All devices shall have covers. Kitchen counter device covers missing. 422.31- All hard wired appliances shall have a disconnecting means. 110.25- lockouts acceptable. Dishwasher
|
Rough-In Permanent Service | 3/4/2019 | 3/4/2019 | 3/4/2019 | P | PASS |
Tom Saunders
|
|
|
Re inspect Phone #: ###-#### Inspection requested via web by Greg Traudt... roiugh ok to cover p/s u/g new ok
|
Rough-In Permanent Service | 3/1/2019 | 3/4/2019 | 3/4/2019 | A | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt... 1) all walls 24" or larger will have a recp outlet - mst bedroom...210.52(A)(2) 2) no p[oint measured horizontally along the floor line of any wall space is more than 6ft from a recp outlet - dining/kitchen wall...210.52(A)(1)
|