Permit Information
Permit NumberELE19-00756
StatusFinaled
Name AMP ELECTRIC
Site Address 7063 W COHO DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: ROUGH IN
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/11/20194/12/20194/11/2019APASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Greg Traudt...finaled 4/11/19
Final4/11/20194/11/20194/11/2019PPASS
DetailsTom Saunders
reinspect...corrections made...ok to final
Final4/9/20194/10/20194/10/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Greg Traudt
300.15- All cables shall terminate in a box. Dishwasher not hooked up.
406.6- All devices shall have covers. Kitchen counter device covers missing.
422.31- All hard wired appliances shall have a disconnecting means. 110.25- lockouts acceptable. Dishwasher
Rough-In Permanent Service3/4/20193/4/20193/4/2019PPASS
DetailsTom Saunders
Re inspect Phone #: ###-#### Inspection requested via web by Greg Traudt...
roiugh ok to cover
p/s u/g new ok
Rough-In Permanent Service3/1/20193/4/20193/4/2019AFAIL
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Greg Traudt...
1) all walls 24" or larger will have a recp outlet - mst bedroom...210.52(A)(2)
2) no p[oint measured horizontally along the floor line of any wall space is more than 6ft from a recp outlet - dining/kitchen wall...210.52(A)(1)