Information based on query as of Friday, May 17, 2024.
Permit Information
Permit NumberELE19-00799
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 1802 N MOUNTAIN COVE RD
Project NameMilitary Reserve Restroom
Customer Number19203
ePlanReviewNo
Description
Alteration: INSTALL NEW 200 AMP, 480V SERVICE, 200A, 208VPANEL
TRANSFORMER AND MISC CONNECTIONS
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/11/201910/11/201910/11/2019APASS
DetailsMark Moncarr
Contact is Bill Hines Phone #: ###-#### Inspection requested via web by Scott Campbell Ok final. GEC run with 2nd grd rod. Backfill is not done yet. Once done, grd rod will be below grade.
Final7/15/20197/16/20197/16/2019AFAIL
DetailsJames Ady
Contact is Bill Hines. Please call one hour prior to inspection, Phone #: ###-#### Inspection requested via web by Scott Campbell No answer No access. Grounding electode conductor cut. Missing ground rod.
Final7/15/20197/16/20197/15/2019ACANC
DetailsJames Ady
Contact: Bill Hines Phone #: ###-#### >> Inspection requested via web by Scott Campbell Inspection cancelled from web by: Scott Campbell
Permanent Service3/20/20193/20/20193/20/2019PPASS
DetailsJames Ady
Bill Phone #: ###-#### Corrections made Available fault current posted. p/s o/h n ok
Permanent Service3/18/20193/18/20193/18/2019PFAIL
DetailsJames Ady
Contact is Ryan Wiedrich Phone #: ###-#### Inspection requested via web by Scott Campbell 110.24 Available fault current needed.