Final | 10/11/2019 | 10/11/2019 | 10/11/2019 | A | PASS |
Mark Moncarr
|
|
|
Contact is Bill Hines Phone #: ###-#### Inspection requested via web by Scott Campbell Ok final. GEC run with 2nd grd rod. Backfill is not done yet. Once done, grd rod will be below grade.
|
Final | 7/15/2019 | 7/16/2019 | 7/16/2019 | A | FAIL |
James Ady
|
|
|
Contact is Bill Hines. Please call one hour prior to inspection, Phone #: ###-#### Inspection requested via web by Scott Campbell No answer No access. Grounding electode conductor cut. Missing ground rod.
|
Final | 7/15/2019 | 7/16/2019 | 7/15/2019 | A | CANC |
James Ady
|
|
|
Contact: Bill Hines Phone #: ###-#### >> Inspection requested via web by Scott Campbell Inspection cancelled from web by: Scott Campbell
|
Permanent Service | 3/20/2019 | 3/20/2019 | 3/20/2019 | P | PASS |
James Ady
|
|
|
Bill Phone #: ###-#### Corrections made Available fault current posted. p/s o/h n ok
|
Permanent Service | 3/18/2019 | 3/18/2019 | 3/18/2019 | P | FAIL |
James Ady
|
|
|
Contact is Ryan Wiedrich Phone #: ###-#### Inspection requested via web by Scott Campbell 110.24 Available fault current needed.
|