Final | 5/30/2019 | 5/30/2019 | 5/30/2019 | A | PASS |
James Ady
|
|
|
GARAGE CODE 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn corrections made final ok
|
Final | 5/24/2019 | 5/24/2019 | 5/24/2019 | A | FAIL |
Rock A. Hudson
|
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn 314.25- Buried recessed can hall out guest bedroom. 410.16- Guest closet shall have completely enclosed lamps. Globe missing.
|
Rough-In Permanent Service | 3/19/2019 | 3/19/2019 | 3/19/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 3/18/2019 | 3/18/2019 | 3/18/2019 | P | FAIL |
Rock A. Hudson
|
|
|
please move inspection to PM today. Phone #: ###-#### Inspection requested via web by Bob Glenn 250.64(D)(1)- Grounding electrode conductor tap shall extend to the inside of each disconnecting means enclosure. Looping through 1 disconnecting means to another creates future difficulties. 300.4- Nail plates needed in kitchen island. 334.12- NM cable shall not be installed where subject to damage. Garage truss pinch point gang nail may damage NM cable.
|
Rough-In Permanent Service | 3/15/2019 | 3/18/2019 | 3/18/2019 | A | CANC |
Rock A. Hudson
|
|
|
Contact Troy with any question or concerns. ###-#### Thanks! Phone #: ###-#### >> Inspection requested via web by Bob Glenn Inspection cancelled from web by: Bob Glenn
|