Information based on query as of Thursday, May 16, 2024.
Permit Information
Permit NumberELE19-01748
StatusFinaled
Name ELECTRICAL AFTER HOURS INC
Site Address 8665 W FRANKLIN RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Wiring of lights and electrical circuits for kitchen equipment
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/1/20197/2/20197/2/2019APASS
DetailsTom Saunders
Mike is the onsite contact. Phone #: ###-#### Phone #: ###-#### Inspection requested via web by Matt Sovic...
ok to final
Final6/30/20197/1/20197/1/2019PNR
DetailsTom Saunders
Mike is the onsite contact. Late afternoon around 4:30 if at all possible Phone #: ###-#### Inspection requested via web by Matt Sovic...
GFCI protection not complete, L/Os not installed on 240V 3 phase equipment, demo of temp lighting, wiring thru grid to outlets above grid needs addressed, panel labelling completed
Electrical Rough-In7/1/20197/1/20197/1/2019PPASS
DetailsTom Saunders
Mike is the onsite contact. Late afternoon around 4:30 if at all possible Phone #: ###-#### Inspection requested via web by Matt Sovic...
grid ok to cover
Final6/27/20196/28/20196/28/2019AFAIL
DetailsDaryl DeGrange
Phone #: 3858813470 >> Inspection requested via mobile web by Caleb Buttars job not complete, apprentices installing electrical devices without supervision.
Electrical Rough-In5/13/20195/14/20195/14/2019PPASS
DetailsJames Ady
1:00 pm would be great if at all possible. Phone #: ###-#### Inspection requested via web by Matt Sovic Corrections made rough in ok walls only
Electrical Rough-In5/13/20195/13/20195/13/2019PFAIL
DetailsJames Ady
Call ahead for lockbox combo - Lance ###-#### // Phone #: ###-#### Inspection requested via web by Matt Sovic 330.12 MC shall not be used where exposed to physical damage.
300.4A1 & 300.4D where ran through holes less than 1 1/4in from the face of framing member, it shall be protected.
Multiple locations through out project.
MC shall not be suppoted to the inside channel of Metal 2x4.