Final | 11/7/2019 | 11/8/2019 | 11/8/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton No card posted. Final ok
|
Electrical Rough-In | 8/27/2019 | 8/27/2019 | 8/27/2019 | P | CANC |
Rock A. Hudson
|
|
|
Please call 30 mins prior Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|
Final | 8/20/2019 | 8/21/2019 | 8/21/2019 | P | PART |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Listings confirmed on furniture whips. All receptacles checked except floor receptacles. TCO to install furniture only OK
|
Electrical Rough-In | 8/16/2019 | 8/19/2019 | 8/19/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Grid complete. Rough in ok cover
|
Electrical Rough-In | 8/16/2019 | 8/16/2019 | 8/16/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 330.30- MC shall be sucred with in 12" of a box. jumpers between boxes and fixture whip exceeding 6'
|
Electrical Rough-In | 8/15/2019 | 8/15/2019 | 8/15/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 330.30- MC shall be secured with in 12" of a box, not including fixture whips. * Popped MC in S,E, office still not repaired. Reception/ lobby area being grouted at time of inspection. Recall when accessible.
|
Electrical Rough-In | 8/13/2019 | 8/13/2019 | 8/13/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton South offices and south hall grid rough in ok cover.
|
Electrical Rough-In | 8/6/2019 | 8/6/2019 | 8/6/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Popped MC S.E. AT PERLIN STRAP. 403 thru 412 grid rough in ok cover
|
Electrical Rough-In | 6/28/2019 | 6/28/2019 | 6/28/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Reception and break room soffits only ok to cover
|
Electrical Rough-In | 6/5/2019 | 6/6/2019 | 6/6/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Confirmed required receptacles for meeting rooms only 1 large enough for floor receptacles and it needs 2. Walls rough in ok cover
|