Permit Information
Permit NumberELE19-02424
StatusFinaled
Name LYNN PROCTOR ELECTRIC
Site Address 225 N 9TH ST Unit: STE 410
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Commercial TI of 4th Floor Space
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/23/20199/23/20199/23/2019PPASS
DetailsJames Ady
Please call Lynn at ###-#### prior to arrival. Phone #: ###-#### Inspection requested via web by Lynn Proctor corrections made final ok
Final9/16/20199/17/20199/17/2019PFAIL
DetailsRock A. Hudson
Please call Lynn prior to arrival. Phone #: ###-#### Inspection requested via web by Lynn Proctor
210.71- Meeting rooms at least 215 sq.ft shall have a receptacle located in the floor. This floor receptacle shall be installed in a listed floor box as per 314.27(B).
All other areas checked out OK. OK to move in furniture.
Electrical Rough-In9/12/20199/12/20199/12/2019PCANC
DetailsRock A. Hudson
Please call Dan prior to arrival. Thank you! Phone #: ###-#### >> Inspection requested via web by Lynn Proctor Inspection cancelled from web by: Lynn Proctor
Electrical Rough-In8/19/20198/20/20198/20/2019PPASS
DetailsRock A. Hudson
Please call Lynn prior to arrival. A ceiling grid inspection is needed. Phone #: ###-#### Inspection requested via web by Lynn Proctor
Grid rough in ok cover
Electrical Rough-In7/8/20197/8/20197/8/2019PPASS
DetailsRock A. Hudson
Please call Lynn prior to arrival. Thank you! Phone #: ###-#### Inspection requested via web by Lynn Proctor
Walls only rough in ok cover