Permit Information
Permit NumberELE19-02438
StatusFinaled
Name HZ ELECTRIC LLC
Site Address 2311 S GEKELER LN
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: WIRING
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/2/201910/3/201910/3/2019APASS
DetailsEric Story
Lock box code 1965 by gas meterr Phone #: ###-#### Inspection requested via web by Hidajet Zahic
Corrections fixed final ok
Final10/2/201910/2/201910/2/2019PFAIL
DetailsEric Story
Lock box code 1965 Phone #: ###-#### Inspection requested via web by Hidajet Zahic
334 Type NM cable shall not be used in a wet location
406 All 120V recetpacles shall be tamper resistant
Electrical Rough-In8/13/20198/13/20198/13/2019PPASS
DetailsRock A. Hudson
Underground to well confirmed direct burial approved, Found label under well head. Rough in ok cover
Rough-In Permanent Service8/12/20198/12/20198/12/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Hidajet Zahic
A inspection is required for underground to well. Provide documentation on underground wire used. Appears to be standard 8-3 NM cable. Tried to call contact, unable to connect.
Underground to service not in at time of inspection.
House rough in ok cover p/s u/g n ok
Rough-In Permanent Service8/11/20198/12/20198/12/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Hidajet Zahic
330.30- Mini split MC cables shall be supported so that no point exceeds 6'. North wall mostly. 1 hanging below trusses.
334.30- NM cables shall be secured with in 12" of boxes and supports not to exceed 4 1/2'.
AC has no support, entry switch above box, bed switch above box, disposal wiring taken apart.
Rough-In Permanent Service7/30/20197/31/20197/31/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Hidajet Zahic
250.24- AC service shall have grounded conductor bonded to a grounding electrode system described in 250.52. No GEC or grounding electrode found.
300.4- Nail plates needed in master bed and family room marked with X.
314.25- Recessed can over master shower shall have junction box cover installed to completely cover opening.
330.12- MC and NM cables shall not be installed where subject to damage. Cut corner at top of north wall.
330.30- Secure and support MC for mini split systems.