Final | 2/3/2020 | 2/3/2020 | 2/3/2020 | P | PASS |
James Ady
|
|
|
garage code 1905 Phone #: ###-#### Inspection requested via web by kevin blackmon corrections made final ok
|
Final | 1/31/2020 | 1/31/2020 | 1/31/2020 | P | FAIL |
James Ady
|
|
|
garage code 1905 Phone #: ###-#### Inspection requested via web by kevin blackmon 210.8 Recep within 6ft of a sink shall be GFCI protected (Up theater wall recep left of balcony door)
|
Rough-In Permanent Service | 10/2/2019 | 10/3/2019 | 10/3/2019 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by kevin blackmon rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 10/2/2019 | 10/2/2019 | 10/2/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by kevin blackmon 110.3- Recessed can covers shall be completely installed. Master hall back cover not tight to box, up theater looks like penched wire. 300.15- Powder bath fan not hooked up. 334.23- Guard strips shall be in place to protect all wiring within 7' of up stairs attic access. 334.30- Up bed NM shall be secured with in 12" of receptacle box. Saw plumber resting pipe on wiring to measure and cut pipe.
|