Final | 11/20/2019 | 11/20/2019 | 11/20/2019 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley Corrections fixed- Final ok
|
Final | 11/18/2019 | 11/19/2019 | 11/19/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley 110.3- 3 outdoor receptacle outlets not working. Not hot. 110.22- Furnace disconnecting means shall be identified. 334.30- Kitchen island, NM cable shall not be installed where subject to damage. Flex installed to protect NM cable shall protect entire length. 342.30- IMC service riser shall be secured in place with in 3' of meter/ panel combo. 356.30- Non-metallic flexible conduit below meter/ panel combo shall be secured with in 12" of termination.
|
Electrical Rough-In | 10/3/2019 | 10/3/2019 | 10/3/2019 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley Rough-in ok to cover whole re-wire
|
Rough-In Permanent Service | 9/13/2019 | 9/16/2019 | 9/16/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley Service only.... p/s o/h n ok
|
Rough-In Permanent Service | 9/12/2019 | 9/13/2019 | 9/13/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley Idaho power requires 16' minimum over residential driveway. Approx. 13 ' at time of inspection. Increase to 16 and recall.
|
Rough-In Permanent Service | 9/11/2019 | 9/12/2019 | 9/11/2019 | A | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Tyler Ridley Inspection cancelled from web by: Tyler Ridley
|