Final | 9/19/2019 | 9/20/2019 | 9/20/2019 | A | PASS |
James Ady
|
|
|
Man door garage code 1224 for entry Phone #: ###-#### Inspection requested via web by Tyler Ridley final ok
|
Final | 9/16/2019 | 9/17/2019 | 9/17/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley 110.3- Open ground shown on east garage wall receptacle. 250.24(A)(1)- Grounding electrode conductor shall be connected to the grounded conductor at the service disconnecting means. At time of inspection bonding of neutral done in panel on load side of service disconnecting means. Grounded conductor shall not be connected to non-current carrying metal parts on load side of service disconnecting means as per 250.24(A)(5). Called number provided and reached someone named Brandy, did not leave message, not sure if right party.
|
Rough-In Permanent Service | 9/16/2019 | 9/16/2019 | 9/16/2019 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley.... installing in panel board (same size) and up grading grounding rough in of garage outlets, new 4 wire to range, and FGCI protection where needed p/s o/h reconnect ok
|