Final | 12/16/2019 | 12/16/2019 | 12/16/2019 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson Final ok
|
Rough-In Permanent Service | 10/3/2019 | 10/3/2019 | 10/3/2019 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson Corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 10/2/2019 | 10/2/2019 | 10/2/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson 210.52(A)(2)- Family room area above 24" tall 8' wide cabinet shall be concidered wall space and shall have receptacles installed. Receptacles shall be located below 5'6". 250.148- Where NM is spliced in a metal box the equipment grounding conductors shall be connected to the box. Pancake boxes. 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from damage. Master bath across from shower. and up front bed. marked with an X. 300.15- NM cable shall terminate in a box. Patio light not stuffed in box. 334.23- Where nm cable is run in attic within 7' of attic access they shall be protected from damage by guard strips. Garage.
|