Final | 12/19/2019 | 12/19/2019 | 12/19/2019 | P | PASS |
Rock A. Hudson
|
|
|
Got the third bonding jumper in. Ask for Robert or Cassie they will take you to the back room thanks! Phone #: ###-#### Inspection requested via web by Trevor Soesbe Final ok
|
Permanent Service | 12/4/2019 | 12/8/2019 | 12/7/2019 | P | PASS |
Rock A. Hudson
|
|
|
After hours inspection Sun. 12/8 PM; contact Trevor Soesbe ###-#### p/s u/g rec ok
|
Conference | 12/4/2019 | 12/6/2019 | 12/6/2019 | P | PASS |
Rock A. Hudson
|
|
|
Call me when your headed that way and I’ll meet you there thanks! Phone #: ###-#### Inspection requested via web by Trevor Soesbe Discussed the changing of 800 amp service, Available fault current for 25k rated mains, grounding electrode system, Fire sprinkler and water main both underground metal water pipes plus has ground rod at I-Line location.
|
Final | 12/4/2019 | 12/9/2019 | 12/4/2019 | A | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Trevor Soesbe //12/4/19 cancel inspection per Daryl D., inspection needed is scheduled for 12/8 //leg
|