Information based on query as of Monday, May 6, 2024.
Permit Information
Permit NumberELE20-01255
StatusFinaled
Name SUBLIME ELECTRIC LLC
Site Address 1426 S COLORADO AVE
Project Name 
Customer NumberCook Bros
ePlanReviewNo
Description
Complete Installation (includes room count and per: Wire for new construction home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/16/20207/17/20207/17/2020APASS
DetailsJames Ady
There will be guys there working. If not there is a key in the pipe between the buildings. If you have any questions please feel free to contact Sam ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Corrections made final ok
Final7/14/20207/15/20207/15/2020AFAIL
DetailsRock A. Hudson
There is a key in the pipe in between the buildings. Call Clay ###-#### with any questions. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 110.22- Furnace disconnecting means shall be labelled. 342.30- IMC service riser shall be secured with in 3' of meter base. 408.4- Circuit directories shall be complete for house and garage. 440.6- Ac overcurrent protection shall not exceed value on name plate. 15 amp max 20 amp installed.
Electrical Rough-In5/4/20205/4/20205/4/2020PPASS
DetailsEric Story
It is open. If you have any questions please feel free to contact Chaz ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
Correction fixed
Rough-in ok to cover
Permanent Service5/4/20205/4/20205/4/2020PPASS
DetailsEric Story
It is open. If you have any questions please feel free to contact Chaz ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
p/s u/g n ok
Rough-In Permanent Service4/30/20205/1/20205/1/2020AFAIL
DetailsRock A. Hudson
It is open. If you have any questions please feel free to contact Chaz ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
110.3- As per manufacturers instructions, 80 to 125 amp breakers shall be installed at lowest position on bus bar, space 125 amp breaker is installed is rated at 50 amp max.
On main level living room recessed can cover shall be completely installed.
210,52(A)- A receptacle outlet shall be located with in 6' of basement bathroom door.
250.32(A)- A grounding electrode system shall be installed at seperate structures, house.
Electrical Rough-In4/8/20204/9/20204/9/2020APASS
DetailsEric Story
This is for the underground. If you have any questions please feel free to contact Clay ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan
U/G ok to cover