INSP-Final Inspection | 1/5/2011 | 1/5/2011 | 1/6/2011 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 12/28/2010 | 12/28/2010 | 12/28/2010 | P | CANC |
Troy Cobbley
|
|
|
To be rescheduled with the two AES permits on Phillippi
|
FIR-Aging Inspection | 12/8/2010 | 12/8/2010 | 12/16/2010 | | NR |
Troy Cobbley
|
|
|
Per Brett he is waiting on a points map for the facp and then will call in the inspection.
|
INSP-Final Inspection | 3/16/2010 | 3/16/2010 | 3/16/2010 | P | FAIL |
Troy Cobbley
|
|
|
The dedicated circuit has been provided but the map and NFPA 72 forms are still needed.
|
INSP-Final Inspection | 10/28/2009 | 10/30/2009 | 10/30/2009 | A | FAIL |
Troy Cobbley
|
|
|
Provide dedicated circuit as per the review comments and NFPA 72 and provide a map at the facp as discussed.
|
INSP-Final Inspection | 9/23/2009 | 9/24/2009 | 9/24/2009 | P | CANC |
Troy Cobbley
|
|
|
No actual inspection was performed. I spoke to Tim on the phone and we discussed the IFC 903.4 requirement for the sprinkler control valves to be supervised by the fire alarm panel. The inspection is to be rescheduled.
|