Permit Number | FIR11-00297 |
Status | Finaled |
Name |
ALARMCO
|
Site Address |
2800 S LIBERTY ST
|
Project Name | CITY OF BOISE PUBLIC WORKS UTI |
Customer Number | |
ePlanReview | No |
Description |
10/7/11 PLAN MODIFICATION (1 initiating device affected): This plan modification is to include a Maglock release, indicate correct wiring for the alarm trouble and supervisory signals, and placement of devices has been corrected to show where the true locations of the existing devices are (no existing devices have been relocated, modified, or replaced).
7/1/11: This fire alarm permit is to replace two FACPs in two of three buildings with zone expanders and control them with an existing main FACP. All three buildings report to the same address, therefore annunciator panels are being installed in all three buildings as well as exterior weatherproof horn/strobes to indicate to the responding personnel which building is in alarm. All annunciators will report the same information simultaneously. An AES radio with an IntelliTap module are replacing the DACT in the main FACP. There is no associated building permit.
NOTE: These building zone expanders and the main FACP must work as a single system, (i.e... the functions of the outer buildings must be able to be controlled/silenced from the main FACP, etc...).
|