INSP-Final Inspection | 9/4/2012 | 9/4/2012 | 9/5/2012 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 8/29/2012 | 8/30/2012 | 8/30/2012 | P | NR |
Forrest France
|
|
|
|
INSP-Supply line flush | 8/27/2012 | 8/27/2012 | 8/27/2012 | P | PASS |
Troy Cobbley
|
|
|
The forward flow test passed.
|
INSP-Sprinkler Rough-in | 8/23/2012 | 8/24/2012 | 8/24/2012 | P | PART |
Troy Cobbley
|
|
|
Earthquaking in the basement has been correct and piping can now be covered. The rough-in for the piping in the Chiller is basically ok except a upright has been installed in a pendant position, one upright needs to be change and installed as a pendant to clear a beam and the hydraulic calculations need to be resubmitted for the chiller room since seven 1" elbows have been installed on one of the branchlines to the heads in the remote area.
|
INSP-Sprinkler Rough-in/Hydro | 8/22/2012 | 8/23/2012 | 8/23/2012 | P | PART |
Troy Cobbley
|
|
|
Todays inspection was a rough to cover in basement and chiller. Earthquake bracing is missing on the 2 1/2" main in the basement. Tyler and I started inspection with the wrong set of plans. We decided to continue the inspection tomorrow with the correct set of plans and the earthquake bracing installed. Also it does not appear that the small orfice heads have been installed in the showers as required on 4/4/2012.
|
INSP-Sprinkler Rough-in/Hydro | 8/13/2012 | 8/14/2012 | 8/14/2012 | A | PASS |
Troy Cobbley
|
|
|
Hydro tests of the overhead systems and the remote FDC supply piping passed.
|
INSP-Sprinkler Rough-in/Hydro | 8/13/2012 | 8/13/2012 | 8/13/2012 | P | FAIL |
Troy Cobbley
|
|
|
Hydro inspection for the overhead system failed due to visable pressure loss at all three guages.
|
INSP-Sprinkler Rough-in/Hydro | 8/9/2012 | 8/10/2012 | 8/10/2012 | P | CANC |
Troy Cobbley
|
|
|
Need a Hydro Inspection Fri 8.10 hoping for 2PM - Tyler Miller is he contact at ###-#### Phone #: ###-#### >> Inspection requested via web by Kindel de Leon Inspection cancelled from web by: Kindel de Leon
|
INSP-Sprinkler Rough-in | 7/11/2012 | 7/12/2012 | 7/12/2012 | P | PASS |
Troy Cobbley
|
|
|
Lay-in tile can be installed. Overspaced heads will be verified later. Heads are overspaced in the Dressing Room. The 9' rule is being used off of two walls. Also the basement mechanical room needs to be resubmitted due to piping and head changes in the remote area.
|
INSP-Sprinkler Rough-in | 6/21/2012 | 6/22/2012 | 6/22/2012 | A | PART |
Troy Cobbley
|
|
|
Corrections in in the attic have been addressed except for the SD heads are too far from the peak as shown measured on the data sheet.
|
INSP-Supply line flush | 6/21/2012 | 6/22/2012 | 6/22/2012 | A | PASS |
Troy Cobbley
|
|
|
The underground supply line flush passed
|
INSP-Sprinkler Rough-in/Hydro | 6/20/2012 | 6/20/2012 | 6/20/2012 | P | PASS |
Troy Cobbley
|
|
|
Chiller room underground hydro test passed.
|
INSP-Sprinkler Rough-in | 6/19/2012 | 6/20/2012 | 6/20/2012 | A | PASS |
Troy Cobbley
|
|
|
Rough In inspection in the attic passed for the most part. It appears that some heads are overspaced from walls are too close together and possibly too far down from the deck. The data sheets for the "Attic" heads was not available on site. The fitter will get data sheet and double check noted items and I will verify at a follow up inspection. I also noted two areas, both at the very east end of the attic, where coverage is lacking.
|
INSP-Sprinkler Rough-in/Hydro | 6/15/2012 | 6/18/2012 | 6/18/2012 | A | FAIL |
Troy Cobbley
|
|
|
Underground Hydro inspection for the chiller room failed due to visable drop in pressure on the guage.
|
INSP-Sprinkler Rough-in/Hydro | 6/11/2012 | 6/12/2012 | 6/12/2012 | A | CANC |
Troy Cobbley
|
|
|
Cancel per phone conversation with Scott Carter
|
INSP-Sprinkler Rough-in | 4/30/2012 | 4/30/2012 | 4/30/2012 | P | PASS |
Troy Cobbley
|
|
|
Remote area #3 piping can now be covered. Pipe routing changes and hydraulic calculations verified by Tim Frost.
|
INSP-Sprinkler Rough-in | 4/30/2012 | 4/30/2012 | 4/30/2012 | A | PASS |
Troy Cobbley
|
|
|
See the city approved plans for additional areas in "area E" where sprinkler piping is ok to cover.
|
INSP-Sprinkler Rough-in | 4/24/2012 | 4/25/2012 | 4/26/2012 | P | PART |
Troy Cobbley
|
|
|
Todays inspection was for Area E. See the approved plans for areas/rooms that are ok for cover. The entire area at remote area #3 needs to be resubmitted prior to approval for cover. Several of the 1" armovers have two to three times the fitting counts that are shown on the plans. The 1 1/4" branchline routing has changed with the installation of bull head tees to re-route the piping and the installation of 45 degree fittings to change elevations due to high ceilings. The wall layout has changed as well. I noted two areas that will be considered combustible concealed spaces that will need to be addressed.
|
INSP-Sprinkler Rough-in | 4/3/2012 | 4/4/2012 | 4/4/2012 | A | PASS |
Troy Cobbley
|
|
|
The sprinkler piping in the Baptistry is ok to cover.
|
INSP-Sprinkler Rough-in | 4/2/2012 | 4/3/2012 | 4/3/2012 | A | PART |
Troy Cobbley
|
|
|
Some piping can be covered. See the latest copy of the approved plans. But the plans do not reflect the actual piping/head arrangement. This is especially important in the hydraulic remote area #4. Additional elbows have been installed in the sprinkler drops that are not shown on the plans. Per plan review there is hardly any safety factor left over so additional fittings will adversely effect the operation of the sprinklers. Plans need to be resubmitted again showing the correct piping layout prior to a cover inspection being given. The remote area #4 is not the only area where piping does not match. One room has additional pendants and uprights where other rooms have pendants and uprights deleted.
|
INSP-Sprinkler Rough-in | 3/15/2012 | 3/16/2012 | 3/16/2012 | A | PART |
Troy Cobbley
|
|
|
See the on site plans for several additional areas where sprinkler piping can be covered. Plan modifications showing all changes and job site construction conditionas need to be submitted for review prior to any more cover inspections due to the amount of changes that have occured to the routing of the sprinkler piping. One area of concern is at Remote Area #4 where a branchline has been deleted, upright protection revises, extended coverage pendant added and additional fittings installed in the piping. Per Tim Frost all of the walls in this area, "D", where to be full height but I saw walls that aren't full height. Also several large rooms have swapped from the south side of the building to the north side of the building. I spoke to Scott, the on site fitter forman, about the issues.
|
INSP-Sprinkler Rough-in | 2/27/2012 | 2/27/2012 | 2/27/2012 | P | PART |
Forrest France
|
|
|
Remainder of overhead work at the west end of waiting 151 at the sheetrock ceiling okayed for cover- see plan set marked and initialed with today's date- contractor to provide missing hanger at one armover as discussed.
|
INSP-Sprinkler Rough-in | 2/13/2012 | 2/13/2012 | 2/13/2012 | P | PASS |
Troy Cobbley
|
|
|
See the city approved for additional rooms that piping is ok to cover.
|
INSP-Sprinkler Rough-in | 2/8/2012 | 2/9/2012 | 2/9/2012 | A | PASS |
Troy Cobbley
|
|
|
UG supply and Remote FDC are ok to cover. The thrust blocks have not been poured against undisturbed soil but per the contractor the surrounding soil, when backfilled, will be compacted to 95%.
|
INSP-Sprinkler Rough-in | 2/6/2012 | 2/6/2012 | 2/6/2012 | P | PASS |
Troy Cobbley
|
|
|
See the as-builts for locations where additional piping can be covered by hard lids.
|
INSP-Sprinkler Rough-in | 1/10/2012 | 1/10/2012 | 1/10/2012 | P | PASS |
Troy Cobbley
|
|
|
A revised set of as-builts were issued today with the date of 1-10-1012. These are now the set of drawings that I'm inspecting to. Anyway area "B" is now approved for cover. I went over possible future issues with Scott about wall heights at the west end of the building and that if the walls are not full height as had been stated to Tim Frost that additional hydraulic calculation areas may be need due to open spaces above the ceilings.
|
INSP-Sprinkler Rough-in | 1/6/2012 | 1/6/2012 | 1/6/2012 | P | CANC |
Troy Cobbley
|
|
|
I notified Scott Carter that I was not comfortable continuing with the inspection due to the issues encountered during yesterdays inspection. Again the remote area in question is down to a 5% cushion due to the pipe routing changes already encountered and now there have been additional fitting added that were not shown on the as-builts of the plan modifications. Plans need to be resubmitted that shown ALL pipe routing changes and additional fittings with the accompanying matching hydraulic calculations prior to any more inspections.
|
INSP-Sprinkler Rough-in | 1/4/2012 | 1/5/2012 | 1/5/2012 | A | PART |
Troy Cobbley
|
|
|
Area "B" was inspected today. The general installation is ok but the 4" main routing has been changed by the addition of four elbows. Plans need to be resubmitted with revised hydraulic calculations due to the remote area only having a 5% cushion. The earth quake bracing is not complete on the 4" main. No cover in area "B" until I can verify the E.Q. bracing.
|
INSP-Sprinkler Rough-in | 12/28/2011 | 12/29/2011 | 12/29/2011 | A | PART |
Tim Frost
|
|
|
Look at several area for cover which were all ok. I marked the areas on the as built drawings of plan mod 1. Also, verify a couple of area for upright protection that was previously denied. These area were also ok.
|
INSP-Sprinkler Rough-in | 12/22/2011 | 12/23/2011 | 12/23/2011 | A | FAIL |
Troy Cobbley
|
|
|
Plan modifications are needed to show the actual pipe routings and pipe sizing used for the installation. I did approve cover on the east corridor that is against the outer walls as per Scott, the superintendant, and I's discussions. As agreed two areas need to be left uncovered to provide access to two additional upright heads that are needed. I also found overspaced heads in the mezzanine level on the south side as well as unbraced sprig ups that exceed 4'
|
INSP-Sprinkler Rough-in | 12/22/2011 | 12/22/2011 | 12/22/2011 | P | CANC |
Troy Cobbley
|
|
|
Miguel Phone #: ###-#### Inspection cancelled from web by: Trent Bice
|
INSP-Sprinkler Rough-in | 12/8/2011 | 12/8/2011 | 12/8/2011 | P | PASS |
Troy Cobbley
|
|
|
The sprinkler piping in rooms 193, 194, 195 and 196 is ok to cover. I also spoke to Scott with Jacobsen Construction about inspections prior to covering.
|
INSP-Conference | 12/6/2011 | 12/6/2011 | 12/6/2011 | P | DONE |
Troy Cobbley
|
|
|
I requested Tim Frost to accompany me to this project to verify possible issues with combustible concealed spaces that I had found on the previous days courtesy inspection. We found many areas which have not been provided upright sprinkler protection and when protection is provided will require many additional sprinkler heads. Per the city approved plans only pendant protection below the ceilings has been provided in these areas. I spoke to the sprinkler fitter and let him know that Plan Modifications will be required. I also spoke to Frank and Ricardo with Jacobsen Construction about a possible stop work order if any more piping is covered and the possibility of removing ceilings just to inspect what has already been installed and covered. No sprinkler rough-in inspections have been performed to this point. I notified Scott and Romeo of the situation.
|
INSP-Sprinkler Rough-in | 5/3/2012 | 5/3/2012 | | P | |
Tim Frost
|
|
|
Chiller Shop rough to cover. please call when in route. Phone #: ###-#### >> Inspection requested via web by Scott Carter II
|