Permit NumberFIR12-00395
StatusFinaled
Name JBL FIRE PROTECTION LLC
Site Address 1487 S GOLDKING WAY
Project NameUnion Square Apartments Bld11
Customer Number 
ePlanReviewNo
Description
The fire sprinkler scope of work consists of protecting a new three floor apartment building per NFPA 13R. The system is supplied with floor level control valves, 1½” FDC and a 2” Backflow Preventer.

The underground is under permit FIR12-00247
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/29/20131/30/20131/30/2013APASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in10/12/201210/12/201210/12/2012PPASS
DetailsTroy Cobbley
The heat tape assembly is ok to be covered.
INSP-Sprinkler Rough-in/Hydro10/9/201210/9/201210/9/2012PPASS
DetailsTroy Cobbley
OH hydro test passed for building 11
INSP-Sprinkler Rough-in10/8/201210/8/201210/8/2012PPASS
DetailsTroy Cobbley
Third floor sprinkler piping can be covered. Tenting has been repaired.
INSP-Sprinkler Rough-in/Hydro10/8/201210/8/201210/8/2012PFAIL
DetailsTroy Cobbley
Overhead hydro test for all three systems failed.Performed the test twice.
INSP-Sprinkler Rough-in9/28/201210/1/201210/1/2012AFAIL
DetailsTroy Cobbley
Third floor tenting has not been repaired or completed. Piping can not be covered.
INSP-Sprinkler Rough-in9/28/20129/28/20129/28/2012PPASS
DetailsTroy Cobbley
Building 11, first and second floor rough-in passed and piping can be covered. Third floor can not be covered until the tenting has been modified. Areas that can not be covered are where the heat tape and associated wiring/control is located when it is installed.