Permit Information
Permit NumberFIR12-00557
StatusFinaled
Name ALARM STAR
Site Address 1875 S CENTURY WAY
Project NameWINGS CENTER
Customer Number 
ePlanReviewNo
Description
This fire alarm permit is to replace an existing manual fire alarm system in an existing building. This system includes a pull station, smoke detector, notification, and sprinkler system monitoring. No HVAC is indicated on the plans.
Associated building permit: BLD11-03007
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/17/20131/17/20131/17/2013PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing1/16/20131/16/20131/16/2013PFAIL
DetailsTroy Cobbley
Retested and sent signals but none were received at central station. All so still need map and as-builts.
INSP-Final Inspection1/15/20131/15/20131/16/2013PCANC
DetailsTroy Cobbley
To be canceled per Rand Phone #: ###-####
INSP-Final Inspection1/14/20131/14/20131/14/2013PFAIL
DetailsTroy Cobbley
For todays inspection we verified strobe spacing in the high ceiling areas. At the east end of the building Rand and I agreed that relocating one strobe in the low ceiling area will provide coverage in another high ceiling area. That work was performed as I waited. The smoke detectors were tested as well. However no signals were received at the monitoring station. To final this project signals need to be received, as-builts provided, map at the facp.
INSP-Final Inspection1/11/20131/11/20131/11/2013PFAIL
DetailsTroy Cobbley
Todays inspection was just verification that the notification circuits and devices functioned.They were out of sync but were repaired. EOL voltage was verified as ok. Candellas were adjusted in several locations due to spacing issues. Spacing was verified on only the low ceiling areas. The high ceilings will need to be checked later. As-builts will be required showing the revised circuits and candellas and additional devices.
INSP-Sprinkler Rough-in12/24/201212/24/201212/24/2012PDONE
DetailsTroy Cobbley
rand and I went over smoke alarms in the daycare area and strobe coverage.
INSP-Final Inspection12/20/201212/21/201212/21/2012PCANC
DetailsForrest France
Rand Phone #: ###-####
INSP-Final Inspection12/20/201212/20/201212/20/2012PCANC
DetailsTroy Cobbley
Notice of NSF check received 12-20-12 for this permit///final inspection cancelled until payment is received - Rand Phone #: ###-####