Permit Information
Permit NumberFIR13-00713
StatusFinaled
Name PHOENIX FIRE PROTECTION
Site Address 406 S VICTORIA DR
Project NameDepot Loft Apartments
Customer Number 
ePlanReviewYes
Description
The fire sprinkler scope of work consists of protection two building three levels each using NFPA 13R. All levels have a typical layout. The sprinklers are spaced at 16x16 residential sprinklers. Each level is a tree with a 1¼” main and 1” lines. There is separate valve room. The riser is equipped with floor level control assemblies.

The underground was installed under permit FIR13-00599

Depot Lofts Apartments - Building #1 - To construct a new 10,960 square foot, three story, wood framed, 12 unit apartment building and related site improvements. This building will be fire sprinkled with a 13R sprinkler system. The sprinklers will be used for a story increase. There are three two bedroom with two bath units, three two bedroom with one bath units and six one bedroom with one bath units. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/15/20147/16/20147/17/2014APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection7/14/20147/15/20147/15/2014PFAIL
DetailsTroy Cobbley
Provide all ot the signs/tags/stickers for the final
INSP-Final Inspection7/14/20147/14/20147/14/2014PCANC
DetailsTroy Cobbley
Cancel per Roy. Will reschedule for tomorrow
INSP-Sprinkler Rough-in/Hydro4/18/20144/21/20144/21/2014APART
DetailsForrest France
Completed hydrostatic testing for both buildings floors 1, 2 and 3. Hydro at the north building 2nd floor failed due to pressure loss at the guage and visible leakage in unit 201. Also noted visible leakage at both buidling riser backflow manifolds- N. bldg upstream of the DCVA , S. bld at the #2 DCVA shutoff. Remainder of floor levels passed OH hydro.
INSP-Sprinkler Rough-in/Hydro4/18/20144/18/20144/18/2014PCANC
DetailsForrest France
Please call Nick 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
INSP-Sprinkler Rough-in4/15/20144/16/20144/16/2014APART
DetailsForrest France
Completed inspection for tenting and insulation at the south building third floor- Okay to cover after adjustments to one area above the kitchen in the north end unit.
INSP-Sprinkler Rough-in4/10/20144/11/20144/11/2014APART
DetailsForrest France
South building 1st and 2nd floor overhead rough-in okayed for cover. One missing hanger added while on site, need to provide matched temp SW heads in the common stairways, patio SW heads to match plan submittals. Third floor cover approval pending tenting and insulation.
INSP-Sprinkler Rough-in4/2/20144/3/20144/3/2014PPART
DetailsForrest France
Verified tenting and insulation at the third floor. Need adjustment above pendent head in the east end unit bedroom as discussed. Remainder okayed for cover.
INSP-Sprinkler Rough-in3/25/20143/26/20143/26/2014APART
DetailsForrest France
Please schedule a rough for 2nd and 3ed floors. Call Nick 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt
INSP-Sprinkler Rough-in3/24/20143/24/20143/24/2014PNR
DetailsForrest France
Please call Nick 30 mins prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt
INSP-Sprinkler Rough-in3/19/20143/19/20143/19/2014PPART
DetailsForrest France
Verified corrections and adjustments at the first floor only. Overspaced hangers at two locations not yet complete. Noted possible light fixture obstructions due to proximity of junction boxes to heads at some locations-
INSP-Sprinkler Rough-in3/17/20143/18/20143/18/2014AFAIL
DetailsForrest France
First floor corrections include; missing hangers at two locations, piping to SW heads incompleted, provide intermediate temp heads at the furnace closets, min. distance between heads is not met at two units, a swing joint at the west end unit appears to be "dry fit".
INSP-Sprinkler Rough-in3/13/20143/13/20143/13/2014ANR
DetailsForrest France
Items noted include missing SW heads per plan at the stair enclosures, need intermediate temp heads in the furnace closets, min. distance from ceiling fans at some rooms are not met.