INSP-Final Inspection | 5/4/2015 | 5/5/2015 | 5/5/2015 | A | PASS |
Katie Marron
|
|
|
Scope of work complete. Permit finaled.
|
INSP-Final Inspection | 4/29/2015 | 4/30/2015 | 4/30/2015 | A | PART |
Katie Marron
|
|
|
Functional test of alarm system complete. Verified previous correction notice items completed satisfactory. Final pending initiating device map posted at FACP and dedicated alarm panel circuit breaker locked out.
|
INSP-Final Inspection | 8/15/2014 | 8/22/2014 | 8/22/2014 | A | CANC |
Troy Cobbley
|
|
|
Cancel per Demetrie Phone #: ###-####
|
INSP-Conference | 8/19/2014 | 8/19/2014 | 8/19/2014 | P | DONE |
Forrest France
|
|
|
Regarding inspection schedule
|
INSP-Final Inspection | 7/24/2014 | 8/1/2014 | 8/1/2014 | A | FAIL |
Forrest France
|
|
|
Completed initial walkthrough. Items noted include; lower manual pull stations per note #18 and plan comments, relocate SD at a storage room 1st floor, remove non-functional existing smoke detectors at various locations 1st floor, adjust visual coverage at two rooms in the dispatch center, SD in mens and womens restrooms 1st floor to be located a min. of 3' from HVAC diffusers, missing SD at the storage closet below the stairs 1st floor, add SD at the 2nd floor mens restroom, revise detector coverage at the storage closet 2nd floor, post points map at the panel per review note #24. Knox box per note # 25 is not installed.
|