INSP-Final Inspection | 2/29/2016 | 3/1/2016 | 3/1/2016 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 2/23/2016 | 2/24/2016 | 2/24/2016 | P | FAIL |
Troy Cobbley
|
|
|
Will be ok to final when the SImplex permit for the dialer is finaled.
|
INSP-Final Inspection | 1/31/2016 | 2/1/2016 | 2/1/2016 | P | FAIL |
Troy Cobbley
|
|
|
See the city approved drawings for list of correctins needed for a final
|
INSP-Final Inspection | 1/28/2016 | 1/29/2016 | 1/28/2016 | P | CANC |
Troy Cobbley
|
|
|
Have appointment in the morning, free after 10:00 all day. Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
|
INSP-Final Inspection | 1/26/2016 | 1/27/2016 | 1/28/2016 | P | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### Inspection requested via web by Brian Richard
|
INSP-Final Inspection | 1/25/2016 | 1/26/2016 | 1/26/2016 | P | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
|
INSP-Alarm Testing | 12/17/2015 | 12/24/2015 | 12/24/2015 | A | DONE |
Jim Page
|
|
|
Notated devices tested on city approved drawings.
|
INSP-Alarm Testing | 12/17/2015 | 12/23/2015 | 12/23/2015 | A | DONE |
Jim Page
|
|
|
Notated devices tested/passed on city approved drawings.
|
INSP-Alarm Testing | 12/18/2015 | 12/22/2015 | 12/22/2015 | P | DONE |
Troy Cobbley
|
|
|
See the city approved plans for corridor detectors tested today. The fire doors did not release upon alarm of the corridor detectors, water flow switch did not function, elevator hat did not function. We tried to test some duct smoke detectors but the units would not turn on.
|
INSP-Alarm Testing | 12/14/2015 | 12/21/2015 | 12/21/2015 | P | DONE |
Troy Cobbley
|
|
|
As-builts are needed showing deleted devices, added devices and address changes. Verified battery size in panel and panel model. Verifed a/v's have been removed per the approved plans. I noted that the smoke detectors for door release will need to be centered on doors. The access controled egress doors will need to be connected to the fire alarm system per the IFC. Interior doors on hold opens need to release on alarm and when the panel becomes inactive as discussed.
|
INSP-Alarm Testing | 12/17/2015 | 12/22/2015 | 12/18/2015 | A | CANC |
Troy Cobbley
|
|
|
>> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
|
INSP-Alarm Testing | 12/14/2015 | 12/16/2015 | 12/14/2015 | P | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
|
INSP-Alarm Testing | 12/14/2015 | 12/17/2015 | 12/14/2015 | P | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
|
INSP-Alarm Testing | 12/14/2015 | 12/18/2015 | 12/14/2015 | A | CANC |
Troy Cobbley
|
|
|
following and during clean agent inspection FIR15-00513 Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
|
INSP-Sprinkler Rough-in/Hydro | 12/14/2015 | 12/18/2015 | 12/14/2015 | P | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brian Richard Inspection cancelled from web by: Brian Richard
|