Permit Information
Permit NumberFIR16-00253
StatusFinaled
Name CURTIS FIRE SPRINKLER SERVICE INC
Site Address 10498 W FAIRVIEW AVE
Project Namechina grand buffet remodel
Customer Number 
ePlanReviewYes
Description
[China Grand Buffet - VIP Banquet Room Expansion] - Quick Permti
modify existing sprinkler ssystm to fit new walls and ceilings inc 2 new dry pendants in new coolers.

(CHINA GRAND BUFFET – VIP BANQUET ROOM EXPANSION) The fire sprinkler system is used for building area increase. To expand an existing 7,125 square foot restaurant to the East into an adjacent 2,366 square foot area. The expansion area includes a 1,164 square foot VIP banquet room. Work is to include interior nonbearing walls, two upgraded restrooms accessible to the disabled, a dropped ceiling soffit, and finishes. Within the existing restaurant, some seating will be removed to create a larger buffet area. Each banquet room has a double leaf exit door that opens directly to the outside. Those doors are required to be maintained in compliance with the Building Code as exit doors. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. A separate fire sprinkler permit shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/15/20166/15/20166/15/2016PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection5/18/20165/19/20165/19/2016AFAIL
DetailsTroy Cobbley
Tile been installed yet.
INSP-Final Inspection5/17/20165/18/20165/18/2016PCANC
DetailsTroy Cobbley
Rescheduled for tomorrow
INSP-Sprinkler Rough-in5/17/20165/18/20165/18/2016PPASS
DetailsTroy Cobbley
insulation has been corrected. Piping can be covered.
INSP-Final Inspection5/16/20165/17/20165/17/2016AFAIL
DetailsTroy Cobbley
Can't cover yet since insulation is still hanging down blocking the upright sprinkler heads in two locations. Also Don and I discussed the overspaced pendants in the Dining area. It looks like he will need to add two pendants to provide the required coverage.
INSP-Sprinkler Rough-in5/11/20165/12/20165/12/2016APART
DetailsTroy Cobbley
General rough-in for the area inspected was ok except that there is deck mounted insulation that is hanging down and ubstructing the upright sprinkler heads and old partition walls that are also blocking upright sprinkler coverage. No piping is to be covered until these items are corrected and a re-inspection has taken place.
INSP-Sprinkler Rough-in4/20/20164/20/20164/20/2016PCANC
DetailsTroy Cobbley
Don Phone #: ###-####
INSP-Conference4/19/20164/19/20164/19/2016PDONE
DetailsTroy Cobbley
Don and I discussed the pendant sprinkler spacing in the dining room. I noted insulation at the roof deck blocking upright heads and possibly overspaced upright against draftstops that are not Dons scope of work but will need addressed prior to a cover inspection being done.