Permit Number | FIR16-00344 |
Status | Finaled |
Name |
ABSOLUTE FIRE PROTECTION
|
Site Address |
1055 E PARKCENTER BLVD
|
Project Name | Albertsons SET Store TI |
Customer Number | |
ePlanReview | Yes |
Description |
[Albertsons SET Store TI]
The fire sprinkler scope of work consists of adding, plugging and relocating sprinklers to accommodate new wall and ceiling configuration, adding a new loading dock, upgrading the fire sprinkle design for the receiving area and adding sprinklers to a new open office area.
Location on Plan - Receiving
Commodity - Grocery
Classification - Class IV
Storage Type (rack, solid pile, etc.) - Racks
Pallet Type (wood or plastic) - Wood
Aisle Width - 8’
Height of Storage - 16’
Ceiling Height - 20’±
Encapsulated - No
Solid Shelves - No
Smoke and Heat Vents - No
Draft Curtain - No
In Rack Sprinklers - No
Sprinkler Type - K=11.2
High Temperature Sprinklers Required - Yes
Applicable NFPA Section - 16.2.1.3.2(d) Curve E, 16.2.1.3.4.1.
Hydraulic Design Criterion - .495/2000 – 65% = .325/2000
Hose Stream Requirements - 500
(ALBERTSONS - SET STORE) Add office area, store staging area, restroom core, and loading dock to existing building shell. Minor demolition of exterior wall and site to accommodate new construction.
|