INSP-Final Inspection | 9/1/2016 | 9/2/2016 | 9/2/2016 | A | PASS |
Jim Page
|
|
|
Previously noted items have been repaired/addressed, final fire alarm inspection passed/complete.
|
INSP-Final Inspection | 8/30/2016 | 8/31/2016 | 8/31/2016 | A | FAIL |
Troy Cobbley
|
|
|
Resubmit plans showing the wire guage change, added strobes, changed candellas. Plans need to address the different NAC panel. I did test the sync which was ok. I did test the interconnection with the new dry pipe riser which was ok. I did not test the duct smoke detectors. Per general contractor security is being installed on the doors but will not hinder exiting in a single motion.
|
INSP-Final Inspection | 8/29/2016 | 8/31/2016 | 8/30/2016 | P | CANC |
Jim Page
|
|
|
Location Access: site is open Installation Technician: Ray McQueen Phone #: ###-#### >> Inspection requested via web by Rose Peterson Inspection cancelled from web by: Rose Peterson
|