Permit NumberFIR16-00557
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 8485 W USTICK RD
Project NameBoise Fire Station #4
Customer Number 
ePlanReviewYes
Description
[Boise Fire Station #4]
The fire sprinkler scope of work consists of protecting a two level fire station with a NFPA 13 system. The system has 6” underground with a 4” riser, backflow preventer and cross mains. The branch lines are 1 ¼” on the first floor and 1 ½” on the second floor.

The underground piping is under permit FIR16-00406

[BLD16-01040] - Permit to construct a new 13,774 square foot fire station. This building is fire sprinklered for area increase and non-separated uses. This building utilizes enhanced lighting to comply with the 2012 IECC / IgCC. Scope of work includes: construction of poured concrete foundation, construction of reinforced CMU exterior walls, construction of new steel bar-joist floor – ceiling framing / steel pan deck, [construction of interior nonbearing walls to create: 10 sleeping units, 8 restrooms / bathing rooms, lobby, two offices, work room, turn out room, decon room, maintenance shop, riser room, SCBA Fill room, 3 storage rooms, laundry room, janitors closet, training classroom, fitness room, and dayroom], new elevator, new electrical, new plumbing, new mechanical, new interior / exterior finishes, new accessible doors / hardware, covered patio on 2nd floor, and related site work. This building is fully fire sprinklered for area increase. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/1/20176/1/20176/1/2017PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection5/30/20175/31/20175/31/2017AFAIL
DetailsTroy Cobbley
All items appear ok except the fan in the Truck Bay is an obstruction and the forward flow test failed.
INSP-Final Inspection5/24/20175/25/20175/25/2017ACANC
DetailsTroy Cobbley
Mark Jensen is the contact for this final inspection. Thank you. Phone #: ###-#### Inspection requested via web by Kay Haney
INSP-Sprinkler Rough-in/Hydro3/31/20174/3/20174/3/2017PPASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover. Hydrostatic test for overhead fire sprinkler piping/FDC complete.
INSP-Sprinkler Rough-in3/30/20173/30/20173/30/2017PPART
DetailsTroy Cobbley
The sprinkler piping above both stairwells, on the second floor, is ok to cover. I noted that additional coverage may be required on the first floor at the bottom of the pole.
INSP-Sprinkler Rough-in2/1/20172/1/20172/1/2017PPASS
DetailsTroy Cobbley
The piping above the second floor restroom and Janitors closet is ok to cover.
INSP-Sprinkler Rough-in12/22/201612/22/201612/22/2016PPART
DetailsTroy Cobbley
The hardlids on the first floor are ok to cover. I noted that branchline restraints are missing and that the plans need to be resubmitted for a plan modification due to pipe routing changes/additional fittings. See note on plan sheet two. The designer contacted me and we spoke of the changes.