INSP-Final Inspection | 12/14/2017 | 12/14/2017 | 12/14/2017 | P | PASS |
Jim Page
|
|
|
Final fire alarm inspection complete, as-builds will be submitted for modifications that were made to system.
|
INSP-Final Inspection | 12/13/2017 | 12/14/2017 | 12/14/2017 | A | FAIL |
Troy Cobbley
|
|
|
Panel and devices passed, smoke and pull tested ok, phone lines tested ok, the 30cd ceiling mount near the facp needs to be relocated or adjusted to a 75cd, a strobe needs to be added in the area just outsside of the facp, as-builts are needed to show these changes, sprinkler devices not tested due to no sprinkler contractor on site. Randy is going to email verification of the signals sent.
FIR17-00727 Phone #: ###-#### Inspection requested via web by Bruce Sullivan
|