Permit Information
Permit NumberFIR17-00774
StatusFinaled
Name TRIBAL FIRE SYSTEMS
Site Address 8000 S FEDERAL WAY
Project NameMicron BLDG51 30-1
Customer Number 
ePlanReviewYes
Description
[Micron Building 51 - System 30-1 - C24074]
The fire sprinkler scope of work consists of a system designed as a 4”x4”x 2½” grid. The system is
designed based on OH II for 3000 ft² per IFC for Semiconductor H5.
• The underground is under permit FIR16-00701
• See addendum for graphic scope of work
[BLD16-03440]
For the construction of a new one story building with a basement for a fabrication and R&D facility to
include related site work. The building includes a 157,037 sq. ft. basement, a 170,997 sq. ft. first story
and a 33,638 sq. ft. equipment platform. This building is fully fire sprinklered and alarmed for H
occupancy. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/12/20198/13/20198/13/2019APASS
DetailsJim Page
Final fire sprinkler inspection for scope of work has been completed. Sprinkler head under added ductwork that was outside scope of work will need to be added before life fire safety final, a seperate permit will be required for obstruction coverage.

CLarence Phone #: ###-####
INSP-Sprinkler Rough-in8/13/20198/13/20198/13/2019APASS
DetailsJim Page
Rough in inpsection for this system has been completed.
INSP-Sprinkler Rough-in/Hydro8/13/20198/13/20198/13/2019ADONE
DetailsJim Page
Hydrostatic test for this system has been witnessed, no pressure loss was observed.