DOC - Permit Finaled | | | 11/25/2019 | | DONE |
|
|
|
|
INSP-Final Inspection | 6/6/2018 | 6/6/2018 | 6/6/2018 | P | CANC |
Troy Cobbley
|
|
|
Still waiting on the outcome of the as-built plans.
As late as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 6/4/2018 | 6/5/2018 | 6/5/2018 | A | FAIL |
Troy Cobbley
|
|
|
Will be ok to final when the as-builts have been accepted.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
INSP-Final Inspection | 6/3/2018 | 6/4/2018 | 6/4/2018 | A | FAIL |
Troy Cobbley
|
|
|
For todays inspection I went through equipment and verified notification device spacing. The candella needs to be changed on several devices and atleast two devices added. We need to test the notification circuit, sprinkler devices and duct smoke detectors. As-builts will be needed as well.
Phone #: ###-#### Inspection requested via web by Nathan Price
|