INSP-Final Inspection | 8/30/2018 | 8/31/2018 | 8/31/2018 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
Roy Phone #: ###-####
|
INSP-Sprinkler Rough-in | 8/29/2018 | 8/30/2018 | 8/30/2018 | A | PASS |
Troy Cobbley
|
|
|
Yesterdays corrections have been addressed. See email dated 8/29/18 addressing issues. Per contractor statement the exterior attached canopy is not a concern, again see email. All overhead piping is ok for cover.
Roy Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 8/28/2018 | 8/29/2018 | 8/29/2018 | A | PART |
Troy Cobbley
|
|
|
Overhead hydro witnessed and passed. Rough-in passed except branchline restraints are needed on almost all of the outriggers and also need to be place correctly on the grid branchlines, need the correct earth quake attachments used or resubmit the ones installed, provide clearance as discussed where the branchlines pass under structural members, provide verification the main entry canopy, which is not shown on the plans, does not require sprinkler protection above or below. Piping is ok to cover, as discussed, except in the areas where I need to re-verify work.
Phone #: ###-#### Inspection requested via web by Chris Green
|
INSP-Final Inspection | 8/27/2018 | 8/28/2018 | 8/28/2018 | P | FAIL |
Jim Page
|
|
|
Rough to cover inspection for overhead fire sprinkler piping has not been completed, overhead hydrostatic test has not been completed. Rough to cover inspection and hydrostatic test must be completed before final inspection can be performed.
Jeff Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 8/2/2018 | 8/3/2018 | 8/3/2018 | A | DONE |
Jim Page
|
|
|
Hydrostatic test for undergorund supply witnessed, no pressure loss observed at riser provided gauge.
UG hydro // Gabe Phone #: ###-####
|
INSP-Supply line flush | 8/2/2018 | 8/2/2018 | 8/2/2018 | P | DONE |
Jim Page
|
|
|
Undergorund main line flush complete.
Gabe Phone #: ###-####
|
INSP-Sprinkler Rough-in | 8/1/2018 | 8/1/2018 | 8/1/2018 | A | PASS |
Jim Page
|
|
|
Rough to cover inspection for undergorund supply complete, approved for cover.
|
INSP-Supply line flush | 7/31/2018 | 8/1/2018 | 8/1/2018 | A | CANC |
Jim Page
|
|
|
Inspection request today was for a rough to cover inspection for underground supply, this request is cancelled and the correct request will be generated.
Gabe Phone #: ###-####
|