Permit Number | FIR18-00621 |
Status | Finaled |
Name |
ALL VALLEY FIRE INSPECTIONS AND SER
|
Site Address |
2141 W AIRPORT WAY
|
Project Name | Airport Business Demo Agent Sy |
Customer Number | |
ePlanReview | Yes |
Description |
1. MH Inergen Computer Room. To remove the Inergen tanks, manifold, pipes and blank off the manual pull/abort and horn strobe. The old Inergen release module will be left in the space and labeled for future use not in service. This action will effectively relegate the Ansul system into a pre-action only system for the pre-action system in the MH computer room. The old pre-action ceiling smoke detectors will be left operational.This system will still be monitored by the building fire alarm system.
2. Old Simplot FM-200 Computer Room. To remove the FM-200 system complete. Tank, manifold, pipes, control panel, smokes, pulls and horn strobes. This system was never monitored by the building fire alarm system. This space is protected by a wet sprinkler system. This work does not appear to be associated with a building permit.
|