Permit NumberFIR18-00628
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 999 W MAIN ST
Project NameOFFICE EVOLUTION TI
Customer Number 
ePlanReviewYes
Description
[Office Evolution TI] - Quick Permit
ADD/RELOCATE SPRINKLERS THROUGHOUT THE TI SPACES PER NFPA 13 2016 FOR LIGHT HAZARD. EXISTING CPVC LINES AND MAINS TO REMAIN IN PLACE.


[BLD18-02387]
This building is fire sprinklered because it is a high-rise. Permit is to remodel an existing 5,741 sq. ft. business space within an existing high rise building. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select interior nonbearing walls, removal of select door/door frames, removal of select millwork, removal of select plumbing fixtures, construction of interior non-bearing walls to create offices, a reception area, a copy/mail area, (2) conference rooms, an IT room, and an open break area, select new door/door frames, extend top of select existing walls to 14’6”, select wall infill, mill work, electrical work, plumbing work, mechanical work and interior finishes in compliance with Ch. 8 of the current IBC. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/6/201811/6/201811/6/2018PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in10/25/201810/26/201810/26/2018APASS
DetailsJim Page
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.

RANDY Phone #: ###-#### Inspection requested via web by Nathan Stenquist
INSP-Sprinkler Rough-in10/4/201810/5/201810/5/2018APART
DetailsTroy Cobbley
Pipe size and hangers appear ok. No ceiling grid has been installed so actual spacing can not be verified yet. Plans need to be approved that show the flex head piping being used.

Randy Phone #: ###-####
INSP-Sprinkler Rough-in10/3/201810/4/201810/4/2018AFAIL
DetailsTroy Cobbley
No city approved plans or small documents on site.


RANDY Phone #: ###-#### Inspection requested via web by Nathan Stenquist