INSP-Final Inspection | 1/2/2019 | 1/4/2019 | 1/4/2019 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
John Howard, Technician Phone #: ###-#### Inspection requested via web by John Siewert
|
INSP-Final Inspection | 12/20/2018 | 12/21/2018 | 12/21/2018 | A | FAIL |
Jim Page
|
|
|
Flow switch did not operate with water flow, FDC bell stopped when panel was silenced, did not continue to ring with flow switch being held, FDC bell needs to ring during water flow.
John Howard, Technician Phone #: ###-#### Inspection requested via web by John Siewert
|