INSP-Final Inspection | 5/20/2019 | 5/20/2019 | 5/20/2019 | P | PASS |
Jim Page
|
|
|
Final fire alarm inspection complete.
please have this aft 3:00 pm if possible call joe 30 min prior to inspect ###-#### Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
INSP-Final Inspection | 5/9/2019 | 5/10/2019 | 5/10/2019 | A | PART |
Mark Scharfen
|
|
|
Tested system. TCO of 10 days granted to verify 6 corrections. Approved by Ron Johnson
ada room strobes do not turn off until reset. sounders in rooms 101, 107, 118 sound steady (bad base).
2 smokes in beam pockets to be lowered to bottom of beam (greater than .1 less than .4)
Phone #: ###-#### Inspection requested via web by Kristin Dolan
|
INSP-Final Inspection | 5/7/2019 | 5/8/2019 | 5/8/2019 | A | FAIL |
Mark Scharfen
|
|
|
Checked candella and smoke placment. Tested sprinkler interconnect and cell monitoring. While testing C wing found several problems:
Sounder bases in room will not resound alarms.
Room 309 bedroom strobe failed.
no ac labels on fire or nac panels.
Cell Dact needs to be added to fire alarm drawing and submitted as an as-build.
access control doors do not drop on fire alarm.
Did not verify horn strobe functionality in rest of building.
Still need to test majority of smoke detectors, CO detectors, access control interface, majority of notification devices.
Please call when in route. We are finalling sprinkler and FA at the same time. Phone #: ###-#### >> Inspection requested via web by Kristin Dolan
|