Permit Information
Permit NumberFIR18-00801
StatusFinaled
Name JOHNSON CONTROLS FIRE PROTECTION SE
Site Address 711 N CURTIS RD
Project NameSA Rehabilitation Hospital
Customer Number 
ePlanReviewYes
Description
PROVIDE AND INSTALL A NEW AUTOMATIC AND MANUAL FIRE ALARM SYSTEM. This work is associated with building permit BLD18-01425.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/19/20197/22/20197/22/2019APASS
DetailsTroy Cobbley
permit finaled


7am // damion Phone #: ###-####
INSP-Final Inspection7/18/20197/19/20197/19/2019AFAIL
DetailsTroy Cobbley
The interconnection with the kitchen hood has been tested but it was brought to my attention that there is a second, small, hood suppression system that is not ready yet. This small suppression system will need to be tested prior to a final on this permit.

Brandon Phone #: ###-####
INSP-Final Inspection7/17/20197/17/20197/18/2019PFAIL
DetailsTroy Cobbley
All items tested except for the kitchen hood interconnect.

Brandon- Phone #: ###-####
INSP-Final Inspection7/5/20197/5/20197/5/2019PPART
DetailsTroy Cobbley
Fire alarm panel verified, phone lines verified, batteries verified, interconnection with tamper switches, PIV switch and flow switches verified. Per Lee the CO detectors need to annunciate in the area covered.


Brandon Phone #: ###-####
INSP-Final Inspection7/1/20197/3/20197/3/2019PFAIL
DetailsTroy Cobbley
Inspection was for basics so that furniture could be moved in. After testing devices we found out that the monitoring account was only a test account. All devices will need to be tested again.

Brandon Phone #: ###-####
INSP-Final Inspection6/26/20197/3/20197/3/2019AFAIL
DetailsTroy Cobbley
PIV does not work, outside alarm bell does not work, no buttset to verify phone lines, no small documents. No testing performed.

first inspection of the day // Kristin Phone #: ###-####