INSP-Final Inspection | 7/19/2019 | 7/22/2019 | 7/22/2019 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
7am // damion Phone #: ###-####
|
INSP-Final Inspection | 7/18/2019 | 7/19/2019 | 7/19/2019 | A | FAIL |
Troy Cobbley
|
|
|
The interconnection with the kitchen hood has been tested but it was brought to my attention that there is a second, small, hood suppression system that is not ready yet. This small suppression system will need to be tested prior to a final on this permit.
Brandon Phone #: ###-####
|
INSP-Final Inspection | 7/17/2019 | 7/17/2019 | 7/18/2019 | P | FAIL |
Troy Cobbley
|
|
|
All items tested except for the kitchen hood interconnect.
Brandon- Phone #: ###-####
|
INSP-Final Inspection | 7/5/2019 | 7/5/2019 | 7/5/2019 | P | PART |
Troy Cobbley
|
|
|
Fire alarm panel verified, phone lines verified, batteries verified, interconnection with tamper switches, PIV switch and flow switches verified. Per Lee the CO detectors need to annunciate in the area covered.
Brandon Phone #: ###-####
|
INSP-Final Inspection | 7/1/2019 | 7/3/2019 | 7/3/2019 | P | FAIL |
Troy Cobbley
|
|
|
Inspection was for basics so that furniture could be moved in. After testing devices we found out that the monitoring account was only a test account. All devices will need to be tested again.
Brandon Phone #: ###-####
|
INSP-Final Inspection | 6/26/2019 | 7/3/2019 | 7/3/2019 | A | FAIL |
Troy Cobbley
|
|
|
PIV does not work, outside alarm bell does not work, no buttset to verify phone lines, no small documents. No testing performed.
first inspection of the day // Kristin Phone #: ###-####
|