Information based on query as of Sunday, May 19, 2024.
Permit Information
Permit NumberFIR18-00837
StatusFinaled
Name ABSOLUTE FIRE PROTECTION
Site Address 1211 W MYRTLE ST Unit: #300
Project NameGuild Mortgate TI
Customer Number 
ePlanReviewYes
Description
[Guild Mortgage TI] - Quick Permit
Ste 300. Relocate 11 SSP and Add 4 SSP for new wall layout. Light Hazard office

[BLD18-03713]
(GUILD MORTGAGE) This building is fully fire sprinklered for 1-hr. substitution. Vanilla shell permit was issued under BLD15-03655 and the core and shell under BLD97-01839. This building has quick response heads installed in the fire sprinkler system FIR10-00590. The corridors are not required to be rated per 2015 IBC 1020.1. Tenant is located on the 3rd floor, suite #300. Scope of work: interior demolition work, new interior non-bearing partition walls, new doors and hardware breakroom millwork, and new interior finish that meets IBC chapter 8 requirements. Ceiling grid and lighting will remain and be altered as needed for repairs in areas of construction. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JHB**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/2/20191/3/20191/3/2019APASS
DetailsJim Page
Final fire sprinkler inspection for area of work complete.

Need to do at 7am Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Final Inspection12/27/20181/2/20191/2/2019ACANC
DetailsJim Page
Need To meet down at the building at 7 AM to set off the alarms. Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
INSP-Sprinkler Rough-in12/3/201812/4/201812/4/2018APASS
DetailsTroy Cobbley
Corrections made. All piping can be covered.

Phone #: ###-#### Inspection requested via web by Sam Ball
INSP-Sprinkler Rough-in12/3/201812/3/201812/3/2018PPART
DetailsTroy Cobbley

Piping is ok to cover but the new branchline is shown to be 1 1/4" and has been installed as 1". Also this new line needs a branch line restraint.

Phone #: ###-#### Inspection requested via web by Sam Ball